background image

Longo programmable controller LPC-2.C05

1 DESCRIPTION

LPC-2.C05 module is used for communication with mobile GSM equipment, like GSM phone or GSM
modem. The communication between LPC-2 system and mobile equipment is established through
SMS messages.

Up to eight digital and  eight analog values could be represented from LPC-2 system as well as up to
eight digital and eight analog commands could be sent from GSM phone or other mobile equipment.
This commands could act direct to digital and analog outputs or can be used for parameter settings.

LPC-2   system   can   works   also   in   alarming   mode,   where   SMS   alarm   message   is   sent   in   case   of
abnormal situation (temperature too high, water leakage, etc.). The SMS alarm messages are sent
recurrently every hour on first three phone numbers stored on the SIM card. If the phone numbers
are stored in the international notation (with country code) then the prefix must start with “

00

and not with “

+

” symbol (e.g. Slovenian international code is 

00

386).

When LPC-2.C05 module is correctly installed and it is ready to operate. In this case status LED1
must blink (refer to the Table 6). The starting sequence is executed once after reset. Complete time
base is 40 sec (see below).

a)

   b)

      c)

a) LED1 blinks once after reset and then is off – SIM card not inserted or SIM card PIN still enabled

b) LED1 blinks once after reset and then is on – GSM network problem; check antenna and GSM signal
level with the mobile phone

c) LED1 blinks once after reset and then start blinking – normal starting sequence; everything OK

IMPORTANT: The PIN number of the SIM card must be disabled otherwise LPC-2.C05 will not be
connected to the GSM network!

Module is powered from internal BUS.

NOTE: For proper system configuration and data allocation please refer to LPC Composer software
help menu.

1

Содержание LPC-2.C05

Страница 1: ...USER MANUAL Longo programmable controller LPC 2 C05 GSM module Version 5 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 388 44 00 e mail info smarteh si www smarteh si...

Страница 2: ...Longo programmable controller LPC 2 C05 Written by SMARTEH d o o Copyright 2012 SMARTEH d o o User Manual Document Version 005 July 1 2012 i...

Страница 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Страница 4: ...o programmable controller LPC 2 C05 1 DESCRIPTION 1 2 FEATURES 2 3 INSTALLATION 3 3 1 Connection scheme 3 3 2 Mounting instructions 5 3 3 Module labeling 7 4 TECHNICAL SPECIFICATIONS 8 APPENDIX A PROG...

Страница 5: ...M card If the phone numbers are stored in the international notation with country code then the prefix must start with 00 and not with symbol e g Slovenian international code is 00386 When LPC 2 C05 m...

Страница 6: ...Figure 1 LPC 2 C05 communication module Table 1 Technical data Dual band 900 1800 MHz Optional RS 232 communication port 9600 bps 8 bits one stop bit no parity no flow control reserved for external A...

Страница 7: ...me Figure 2 Connection scheme Table 2 ANT ANT Antenna connector SMA F GSM antenna SMA M Table 3 SIM CARD SIM CARD SIM card connector Table 4 K1 Internal BUS Data DC power supply Connection to I O modu...

Страница 8: ...FF power off Blink once SIM card not inserted or PIN enabled ON SIM status OK NET Green LED indicates C05 Network state OFF power off Blink once ON Low GSM signal ON SIM status OK Status Green LED ind...

Страница 9: ...with LPC 2 C05 module to the antenna connector 4 Mount other LPC 2 modules if required Mount each module to the DIN rail first then attach modules together through K1 and K2 connectors 5 Switch ON mai...

Страница 10: ...e code 04 year of code opening 001 derivation code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 16 05 is the date code 16 week and 05 year of production Label 2 descriptio...

Страница 11: ...no flow control reserved for external AT commands Antenna connector SMA M Antenna impedance 50 Phone book capacity 100 SMS storage capacity 40 in ME mobile equipment up to 25 in SIM SIM dependent Freq...

Страница 12: ...6 BIT7 Range 0 1 Address MC3 0x1069 N 0x0040 MC7 0x0702 N 0x0040 Boolean variables Tx used to select the number of analogue BIT0 BIT3 and digital BIT4 BIT7 input signals I O Module FBOOL8 I O Name BIT...

Страница 13: ...I O Module FWORD16 I O Name WORD1 WORD2 WORD3 WORD4 WORD5 WORD6 WORD7 WORD8 Range 0 65535 Address MC3 0x143a N 0x0040 MC7 0x0103 N 0x0040 Boolean variable Tx used for alarming of the LPC 2 system s I...

Страница 14: ...he following table describes all the changes to the document Date V Description 1 7 2012 005 CGP General update New HW and FW version 11 5 2010 004 Updated warranty permanence 30 6 2005 003 The initia...

Страница 15: ...Longo programmable controller LPC 2 C05 6 NOTES 11...

Отзывы: