Longo Modbus Products LMP-1.MP2
4.5 Modbus RTU settings memory
Table 6: Holding Registers
Memory
Variable description
Range
Values
40090
0/12345
0 -> 12345 = EEprom Write
40091
Not used
40092
Not used
40093
Not used
40094
Not used
40095
Temperature Offset
-1000 .. +1000
-10.00 °C .. +10.00 °C
40096
Touch button Off sensitivity limit
1 .. 20
High sens. .. Low sens.
40097
Touch button On sensitivity limit
1 .. 20
High sens. .. Low sens.
40098
Modbus RTU slave address
1 .. 255
Default address is 1
40099
Modbus RTU Baud rate
NOTE: polling cycle faster than
500 msec can cause occasionally
timeout warnings.
0 .. 11
0 = 19200 bps (default)
1 = 600 bps
2 = 1200 bps
3 = 2400 bps
4 = 4800 bps
5 = 9600 bps
6 = 14400 bps
7 = 19200 bps
8 = 38400 bps
9 = 56000 bps
10 = 57600 bps
11 = 115200 bps
Other = 19200 bps
40100
Modbus RTU Parity
0 .. 3
0 = None
1 = None
2 = Odd
3 = Even (default)
Other = None
2 On change from 0 to 12345 the RTU settings memory (40091..40100) will be updated into the module Eeprom.