background image

0017A3    

Device unlocking

If the device has been locked, an 

Allen key will be required for 

unlocking.

Depress the locking mechanism, 

by inserting the Allen key, or 

similar, into the device’s cavity 

and pushing (A).

Simultaneously twist the device 

anti-clockwise to release (B).

     IMPORTANT

(A)

!

Remove dust cover before use.

The device should be tested upon installation and in accordance with local 

requirements.

Testing should only be carried out by a fully trained competent person.

The manufacturer recommends regular functional testing in accordance with 

local codes of practice.

Cleaning and repairs must be undertaken by the manufacturer’s authorised 

representative.

Do not open the case to clean inside the detector.

7  Optional device locking

(B)

Reassemble the device as shown below.

  

9

  

8  Completing the installation

Operating temperature   

-10 to +55 °C 

 

Storage temperature 

 

With batteries 

 

 

-10 to +30 °C

Without batteries  

 

-10 to +55 °C

Humidity 

 

 

0 to 95% noncondensing

Location / IP rating 

 

Type A: for indoor use / IP33

Supply   

 

 

3 x ER14505M 3.6 V lithium thionyl chloride

    batteries 

(Fanso 

or 

Titus)

CAUTION! 

Operating voltage 

 

2.7 to 3.65 VDC

Current consumption 

 

0.32 A max.

Power consumption 

 

0.8 W max.

Operating frequency 

 

868 MHz

Output transmitter power  

14 dBm / 25 mW

Signalling protocol 

 

X5

Detector sensitivity and   

Smoke: Normal*†, AVF,

responsivity settings  

 

Heat: 58°c static (A2S)*†, 58c rate of rise (A2R)*,

 

 

 

 

72°c static (BS)* & 72°c rate of rise (BR)*

*  EN54 approved sensitivities   

  Default dual sensitivities   

Sounder output    

 

93 dB(A) at 1m max.

For full sounder output information, refer to the Sounder Data doc (MK103).

Beacon coverage  

 

C-3-12 (WHITE flash) / C-3-9.5 (RED flash)

Beacon flash rate  

 

0.5 Hz (1 flash, every 2 seconds)

Dimensions (Ø x D) 

 

110 x 61 mm

Specification

Certification
Certification body
CPR DoP

0905

19

EN54-3:2001. Incorporating amendments nos. 1 and 2. Fire 

detection and fire alarm systems. Part 3: fire alarm devices - 

sounders.

 

                 

EN54-5:2001. Incorporating amendment no. 1. Fire detection 

and fire alarm systems. Part 5: heat detectors - point 

detectors.
EN54-7:2001. Incorporating amendment no. 1. Fire detection 

and fire alarm systems. Part 7: smoke detectors - point 

detectors using scattered light, transmitted light or ionization.
EN54-13:2005. Fire detection and fire alarm systems.    

Part 13: compatibility assessment of system   components. 
EN54-23:2010. Fire detection and fire alarm systems.    

Part 23: fire alarm devices. Visual alarm devices. 
EN54-25:2008. Incorporating corrigenda September 2010 and 

march 2012. Fire detection and fire alarm systems. Part 25: 

components using radio links.
EMS declares that the radio equipment type SmartCell Dual 

Detector With Combined Sounder Beacon is in compliance 

with Directive 2014/53/EU. The full text of the EU declaration 

of conformity is available at the following internet address: 

www.mysmartcell.com
2012/19/EC (WEEE directive): Products marked with this 

symbol cannot be disposed of as unsorted municipal waste 

in the European Union. For proper recycling, return this 

product to your local supplier upon purchase of equivalent 

new equipment, or dispose of it at designated collection 

points. For more information see www.recyclethis.info

Dispose of your batteries in an environmentally friendly 

manner according to your local regulations.

European Union 

directives

Approved to

Manufacturer

Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24. 

39-100 Ropczyce, Poland

Year of manufacture See devices serial number label 

0359-CPR-00268

Regulatory information

The device includes an optional locking mechanism.

Remove the thin section of plastic shown below.

Once locked, the Allen key will be required

to unlock the device.

©2021 EMS Ltd.  All rights reserved.                                                                                                       Page 1 of 2 

 

TSD091-0001-99 (Issue 4) 25/08/2021 AJM                                                                                                                                                                                                                                                        

©2021 EMS Ltd.  All rights reserved.                                                                                                       Page 2 of 2 

 

TSD091-0001-99 (Issue 4) 25/08/2021 AJM                                                                                                                                                                                                                                                       

This is a life safety product. Only use manufacturer approved battery types. 

Failure to do so may result in damage to the product.

DO NOT mix batteries of different type or age.

When replacing batteries; remove all old batteries before fitting replacements.