Page 18
25
RH Max
Value
This option permits you to select the highest RH value to be
used by the SMT-IAQ. RH above this value will be ignored.
(See Graph on page 6).
Default is 100%. Adjustments are 0-100% on 5% steps.
26
RH Low Voltage
This sets the RH 0-10V output minimum voltage when at
the minimum RH value (see Graph on page 6).
Default is 0v. Adjustments are 0-10V in 0.5V steps.
27
RH Max Voltage
This sets the RH 0-10V maximum output voltage when at
the maximum RH value (see Graph on page 6).
Default is 10v. Adjustments are 0-10V in 0.5V steps.
28
RH Safety
Voltage
This sets a constant voltage to the RH 0-10V output.
This voltage will be present whenever the SMT-IAQ is
powered (see Graph on page 6).
Default is 0v. Adjustments are 0-10V in 0.5V steps.
29
CO2
Min
Value
This option permits you to select the lowest CO2 value to
be used by the SMT-IAQ. CO2 levels below this value will be
ignored. (See Graph on page 6).
Default is 0ppm. CO2 Adjustments are 0 to 2000ppm in
50ppm steps.