Display

CPF

EPR

-OV-

     -LV-

OH

Display

OC-S

OC-D

OC-A

OC-C

OV-C

Err4

OVSP

Error

Cause

Remendy

PROGRAM PROBLEM 

External noise interference

Connect a parallel RC burst

absorber across the magnetizing

coil of the magnetic contactor

that causes interference

Voltage too low

during stop

1. Power voltage too low

2. Restraining resistor or fuse

burnt out.

3. Detection circuit

malfunctions

1. Check if the power voltage

was correct or not

2. Replace the restraining

resistor or the fuse

3. Send the inverter back for

The inverter is

overheated

during stop

1. Detection circuit

malfunctions

2. Ambient temperature too high

or bad ventilation

1. Send the inverter back for

repairing

2. Improve ventilation

conditions

EEPROM

problem

Faulty EEPROM

Replace EEPROM

Voltage too high

during stop

Detection circuit malfunction

Send the inverter back for

repairing

Over current at

start

1. the motor wind and

enclosure short circuit

2. the motor contacts and earth

short circuit

3. the IGBT module ruined

1.inspect the motor

2.inspect the wire

3.replace the transistor module

Over-current at

deceleration

The preset deceleration time is

too short.

Set a longer deceleration time

Errors which can be recovered manually and automatically

Error

Cause

Remendy

Voltage too high

during operation/

deceleration

1. Deceleration time setting too

short or large load inertia

2. Power voltage varies widely

1. Set a longer deceleration time

2. Add a brake resistor or brake

module

3. Add a reactor at the power input

side

4. Increase inverter capacity

Illegal interrupt

of CPU

Outside noise interference

Send back to repair if it happens

many times

Over-current at

acceleration

1. Acceleration time too short

2. The capacity of the

motor higher than the

capacity of the inverter

3. Short circuit between

the motor coil and the

shell

4. Short circuit between

motor wiring and earth

5. IGBT module damaged

1. Set a longer acceleration time

2. Replace a inverter with the

same capacity as that of the

motor

3. Check the motor

4. Check the wiring

5. Replace the IGBT module

Over-current at

fixed speed

1. Transient load change

2. Transient power change

1.Increase the capacity of the

inverter

2.Rerun parameter auto tuning

(0-06 = 1)

3. Reduce stator resistance (14-0)

if the above remedies are

helpless

Over speed during

operating

1. Motor load too big or Inverter

capacity too small

2. Motor parameter error

(vector mode)

3. The gain is too big during

vector mode operating

4. The Current detect circuit

fault

1. Increase acceleration /

deceleration time (3-02/3-03)

2. Input correct motor

Parameter

3.Change stator Resistance gain

and Rotator resistance gain

(14-0/14-1), suggest that

decrease 50~100, until 0

4. Send back to SMACH.

Errors which can not be recovered manually

*Error display and remedy 

*Error which cannot recovered manually 

 

 

 

 

 

 

 

 

Содержание EFE 4000

Страница 1: ...SOFT SERVE AND FROZEN YOGHURT FREEZER SERVICE MANUAL MODEL EFE 4000 Manual Number V 001 17 05 2012...

Страница 2: ...pansion Valve Adjustment 2 Refrigeration System Schematic 3 Control Functions 4 Air Adjustment 5 Electrical System 6 Troubleshooting General Inverter 7 Inverter Control by a Laptop 8 Bacteria Troubles...

Страница 3: ...ressure higher or lower by turning the expansion valve adjustment screw Clockwise turns will raise the pressure and counterclockwise will lower the pressure Bear in mind that In this model 360 turning...

Страница 4: ...t cools down the mix in the cylinder around 6C when beater turns Machine checks the current in the beater motor by an inverter when the current is around 2 6Amp for soft mode 2 8 Amp for hard mode it...

Страница 5: ...unt of aeration is desired The setting can be changed during operations by simply turning the INNER aeration tube to the desired size hole The SMALL HOLE will increase air percentage in the Soft Serve...

Страница 6: ...6 5 ELECTRICAL SYSTEM...

Страница 7: ...7...

Страница 8: ...out dispensing ice cream Take out ice cream untill fresh mix is filled in cylinder Ice cream dispensed is too fast Do not exceed the production shown in the capacity 6 Mix or ice cream comes out from...

Страница 9: ...vel 8V L level 2V PNP only LEVEL SENSOR Common contact for S1 S5 S6 S7 in PNP Source input Short circuit pin 2 and pin 3 refer to SYNPLUS wiring diagram of SW1 when used PNP input Rotary switch optica...

Страница 10: ...celeration time setting too short or large load inertia 2 Power voltage varies widely 1 Set a longer deceleration time 2 Add a brake resistor or brake module 3 Add a reactor at the power input side 4...

Страница 11: ...th the load 2 Increase inverter capacity 3 Improve ventilation conditions Inverter overload Heavy Load Increase the inverter capacity Over torque 1 Heavy Load 2 Insufficient settings of 9 14 9 15 1 In...

Страница 12: ...a Stop command then a Run command to the inverter for it to be restarted 3 Stop key cannot perform emergency stop when 1 03 0001 External emergency stop The inverter will ramp stop and then flash E S...

Страница 13: ...ent detection circuit is abnormal If Reset inverter is not available please send the inverter back for repair Parameter setting error 1 3 01in the range of 3 13 3 16 or 3 14 3 16or 3 15 3 16 2 3 00 3...

Страница 14: ...y abnormalities in the inverter See error descriptions to check wiring and correct if necessary Is forward or reverse running command issued Motor speed varies unusually Is the load too heavy Reduce t...

Страница 15: ...15 Quick Troubleshooting of Inverter...

Страница 16: ...16 InverterFault...

Страница 17: ...17...

Страница 18: ...18 Inverterfault...

Страница 19: ...7 INVERTER CONTROL BY A LAPTOP Inverter settings can be changed by the program named SYNPLUSand to connect to inverter over a laptop RS232 cable is needed Then follow the instructions to change settin...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...terms of human health Lack of them results in high bacteria counts when a sampling is taken by a sanitarian Bacteria counts should not exceed the following figures Therefore in a daily basis all machi...

Страница 25: ...25...

Страница 26: ...e temperature of the mix poured into the hopper is around room temperature It must take the temperature around 4C To control the hopper temperature panel and check the thermostat as seen in the photo...

Страница 27: ...27 9 EXPLODED VIEWS...

Страница 28: ...28...

Страница 29: ...29...

Страница 30: ...30...

Страница 31: ...31...

Отзывы: