Battery Management
SMA
Technologie AG
Page 36
SI3324/4248-14:FE2406
User Manual
6.1
Charge Control
The Sunny Island 3324/4248 has a 3-level charge control using the IV
0
V process.
The I stands for the bulk phase. At this level, the charging is only limited by the
defined maximum battery current ("23-4 AmpdcBatMax" parameter) or by the
maximum generator current ("24-2 AmpacGenMax" parameter). During this phase
the battery voltage increases as the batteries are charged.
Once the battery voltage has reached the value defined for the second phase V
0
,
then the constant voltage charging (absorption phase) begins. At this level, the
battery voltage is maintained at a constant level, resulting in a continually decreasing
battery current. The Sunny Island 3324/4248 remains in this phase for the period of
time defined for this phase (parameters "12-6 TabsorbLeft").
Once this phase is finished, the Sunny Island 3324/4248 enters the float charge that
again provides constant current charging but at a greatly reduced charging voltage.
If charging is done from a generator, then this is stopped on entry to this phase, thus
ending charging of the batteries at this point. The Sunny Island 3324/4248 remains
in this phase until either more than 30 % of the nominal capacity has been used (all
discharges are summed) or the generator is automatically restarted (see section 5.2
"Generator Parameters" (page 29)).
Содержание Sunny Island 3324
Страница 1: ...Sunny Island 3324 4248 User Manual User Manual Version 4 0 SI3324 4248 14 FE2406 TBE SI4248 ...
Страница 2: ......
Страница 6: ...SMA Technologie AG Page 6 SI3324 4248 14 FE2406 User Manual ...
Страница 8: ...Notes on this Manual SMA Technologie AG Page 8 SI3324 4248 14 FE2406 User Manual ...
Страница 14: ...The Sunny Island 3324 4248 SMA Technologie AG Page 14 SI3324 4248 14 FE2406 User Manual ...
Страница 42: ...Frequency Shift Power Control FSPC SMA Technologie AG Page 42 SI3324 4248 14 FE2406 User Manual ...
Страница 44: ...Automatic Frequency Adjustment SMA Technologie AG Page 44 SI3324 4248 14 FE2406 User Manual ...
Страница 60: ...Troubleshooting Problem Solving SMA Technologie AG Page 60 SI3324 4248 14 FE2406 User Manual ...
Страница 64: ...CE Declaration of Conformity SMA Technologie AG Page 64 SI3324 4248 14 FE2406 User Manual ...
Страница 66: ...Contact SMA Technologie AG Page 66 SI3324 4248 14 FE2406 User Manual ...
Страница 75: ...SMA Technologie AG User Manual SI3324 4248 14 FE2406 Seite 75 ...
Страница 77: ......
Страница 78: ......
Страница 79: ......