SMA America, LLC
34
SCUS-BE-BUS111113
User Manual
7.1 Diagnosis
The displayed faults are divided into the three areas of the PV system:
• PV generator (see Section 7.1.1 ”PV Generator Fault” (page 34)).
• Sunny Central (see Section 7.1.2 ”Sunny Central Fault” (page 35)).
• Grid (see Section 7.1.3 ”Grid Fault” (page 37)).
7.1.1 PV Generator Fault
If the fault is on the PV generator side, a two-digit error code
appears on the left side of the system display (see figure to the
right: A). With this error number you can narrow down the
type of malfunction. The table below describes the type of
fault, its cause and what you can do to rectify the fault.
No.
Description
34
Error text:
DC-Overvoltage
Cause of fault:
The voltage of the PV generator is too high.
Corrective measures:
• Immediately disconnect the PV generator from the Sunny Central! The Sunny
Central can be damaged by the high input voltage.
• Check the input voltage.
• Check module wiring and system design.
35
Error text:
Ground Fault
Cause of fault:
The PV generator has a connection to ground.
Corrective measure:
• Check the PV generator for a ground fault.
Содержание SUNNY CENTRAL 250U
Страница 2: ......
Страница 45: ...SMA America LLC User Manual SCUS BE BUS111113 45 ...
Страница 46: ...SMA America LLC 46 SCUS BE BUS111113 User Manual ...
Страница 47: ......
Страница 48: ...4 NFSJDB 1SPEVDUJPO XXX SMA ANFSJDB DPN ...