SMA America, LLC
28
SCUS-BE-BUS111113
User Manual
6 Parameters
6.1 Description of Parameters
The following table shows the parameters that are visible to the user. The installation guide of the
Sunny Central also shows the parameters that are visible to the installer.
Parameter Name Range
Default
Parameter Description
Ackn
–––, Ackn,
NoAckn
–––
Acknowledge an error manually
You can acknowledge an error with the
optional Sunny WebBox. Refer to
Section 7.1.6 ”Acknowledge the Error
with the Sunny WebBox” (page 40).
CardFunc
–––, ForcedWrite,
StoEvtHis,
StoFailHis
–––
Saving ring memory with errors and
events on SD card.
ChkGdFrqLo
57 ... 59.8 Hz
59.3 Hz
Minimum frequency for Sunny Central
operation.
If the frequency drops below the value
given in ChkGdFrqLo, the Sunny Central
will shut down after the time period given
in ChkGdFrqLoT.
ChkGdFrqLoT
160 ... 300000 ms 160 ms
ChkGdFrqMax
60.5 ... 64.5 Hz
60.5 Hz
Maximum frequency for Sunny Central
operation.
If the frequency exceeds the value given
in ChkGdFrqMax, the Sunny Central
shuts down immediately.
ChkGdFrqMin
57 ... 59.8 Hz
57 Hz
Minimum frequency for Sunny Central
operation.
If the frequency drops below the value
given in ChkGdFrqMin, the Sunny
Central shuts down immediately.
ChkGdVtgHi
288 ... 321.3 Vrms 304.7 Vrms
Maximum voltage for Sunny Central
operation.
The Sunny Central shuts down within 1
second in case the voltage exceeds the
value defined in ChkGdVtgHi.
ChkGdVtgLo
149.6 ... 265.9
Vrms
243.8 Vrms
Minimum voltage for Sunny Central
operation.
The Sunny Central shuts down within 2
seconds in case the voltage exceeds the
value defined in ChkGdVtgLo.
Содержание SUNNY CENTRAL 250U
Страница 2: ......
Страница 45: ...SMA America LLC User Manual SCUS BE BUS111113 45 ...
Страница 46: ...SMA America LLC 46 SCUS BE BUS111113 User Manual ...
Страница 47: ......
Страница 48: ...4 NFSJDB 1SPEVDUJPO XXX SMA ANFSJDB DPN ...