Electrical Connection
SMA
Technologie AG
32
SB40TL_50TL-IEN081211
Installation Guide
Additional grounding of the housing
If a second protective earth connection is required in the installation country (e.g. Switzerland), you
can also ground the Sunny Boy with an additional protective earth on the connection terminal of the
housing.
Proceed as follows:
1.
Loosen screw (A) halfway.
2.
Insert the stripped grounding cable (D) under the
terminal clamp (max. cross section: 16 mm²).
3.
Screw the terminal (C) tight.
The toothing of the washer (B) must face toward
the terminal clamp.
You can ground multiple Sunny Boys as shown below:
NOTICE!
High leakage currents can damage the Sunny Boy!
•
Do not ground any modules on the terminal for ground connection cables in the
Sunny Boy.
A
B
C
D
Содержание SUNNY BOY 4000TL
Страница 6: ...SMA Technologie AG 6 SB40TL_50TL IEN081211 Installation Guide...
Страница 16: ...Technical Data SMA Technologie AG 16 SB40TL_50TL IEN081211 Installation Guide Efficiency curve...
Страница 73: ...SMA Technologie AG Contact Installation Guide SB40TL_50TL IEN081211 73...
Страница 74: ...Contact SMA Technologie AG 74 SB40TL_50TL IEN081211 Installation Guide...