SB3800U-12:SE2006
SMA America
3-3
Dimensions and Recommended Clearances
The outer dimensions of the SB3800U are shown in Figure 3-2. The SB3800U must be
mounted so that there is at least eight inches of clearance around it.
Figure 3-2 Outer Dimensions of the SB3800U
CAUTION: You
must
ensure that there is sufficient clearance for
the flow of the air around the SB3800U! In a normal operating
environment with good ventilation, eight inches of clearance is
adequate.
Note:
The National Electrical Code may require significantly
larger working clearances (see NEC Section 110.26).
Störung
Failure
Betrieb
Operation
Erdschluss
Earth Fault
236 mm
(9.3 in)
351 mm
(13.83 in)
452 mm
(17.80 in)