Commissioning
SMA Solar Technology AG
28
SB11_17-IEN084820
Installation Guide
PV Overvoltage
Check DC voltage!
• Higher than maximum input voltage: contact the planner / installer of the PV generator for
assistance.
• Lower than maximum input voltage: reconnect the Sunny Boy to the generator as described in
section 5.2 „Connecting the PV Generator (DC)“ (16).
If the message occurs again, disconnect the Sunny Boy again and contact the SMA Service Line
(see section 13 „Contact“ (44)).
6.2 Blink Codes
Overview
NOTICE!
Excessive DC input voltage can destroy the Sunny Boy!
• Disconnect the grid voltage and the
PV generator from the grid if, after a short
period of time, the bottom yellow LED
lights up repeatedly 4 times at intervals of
one second and the display shows the
accompanying message.
Green
Red
Yellow
Status
glows continuously
does not glow
does not glow
OK (feeding operation)
glows continuously
does not glow
disturbance
glows continuously OK (initialization)
flashes quickly
(3 x per second)
does not glow
does not glow
OK (stop)
glows continuously
does not glow
disturbance
flashes slowly
(1 x per second)
does not glow
does not glow
OK (waiting, grid monitoring)
glows continuously
does not glow
disturbance
briefly goes out
(approx. 1x per second)
does not glow
does not glow
OK (derating)
glows continuously
does not glow
disturbance
does not glow
does not glow
does not glow
OK (night shutdown)
glows/flashes
disturbance
glows continuously
does not glow
disturbance
glows/flashes
disturbance