AC Voltage Configuration
SMA America, LLC
24
SB50US-80US-eng-IUS112633
Installation Guide
The following figures display the correct arrangement of the jumpers for the 240 V Delta system
configuration: Note the order in which the inverters are connected to the phases.
Configuration Examples for Jumpers with 240 V Delta, 120 V Stinger
Configuration Examples for Jumpers with 240 V Delta, Grounded
When using grounded 240 V or 208 V Delta grids, connect terminal L2 to the grounded
phase.