11 Troubleshooting
SMA Solar Technology AG
Operating manual
STP3-6-3AV-40-BE-en-13
88
Event number
Message, cause and corrective measures
10340
Webconnect disabled
The Webconnect function has been disabled.
10502
Active power limit AC frequency
The inverter has reduced its power due to a too-high power frequency to en-
sure grid stability.
Corrective measures:
• If possible, check the power frequency and observe how often
fluctuations occur. If fluctuations occur frequently and this message is
displayed often, contact the grid operator and request approval to
change the operating parameters of the inverter. If the grid operator
gives his approval, discuss any changes to the operating parameters with
the Service.
10901
Self-test start [xx]
The self-test is running.
10902
Current disconnection limit for voltage increase protection [xxx] V
Preliminary result of the self-test
10903
Current disconnection limit for voltage monitoring lower maximum
threshold [xxx] V
Preliminary result of the self-test
10904
Current disconnection limit for voltage monitoring upper minimum
threshold [xxx] V
Preliminary result of the self-test
10905
Current disconnection limit for voltage monitoring middle minimum
threshold [xxx] V
Preliminary result of the self-test
10906
Current disconnection limit for frequency monitoring switchable maxi-
mum threshold |xxx| Hz
Preliminary result of the self-test
10907
Current disconnection limit for frequency monitoring switchable mini-
mum threshold [xxx] Hz
Preliminary result of the self-test
10908
Current disconnection limit for frequency monitoring switchable mini-
mum threshold [xxx] Hz
Preliminary result of the self-test
10909
Current disconnection limit for frequency monitoring upper minimum
threshold [xxx] Hz
Preliminary result of the self-test