background image

1  Definition of Active Power, Reactive Power and Apparent Power

SMA Solar Technology AG

4

IPC_STP-TI-en-14

Technical Information

Calculating Apparent Power

The sum of active power and reactive power is the so-called apparent power S (unit: VA; volt-ampère). It should be noted 

that the units are not simply added arithmetically, but must be represented as vectors: active and reactive power form the 

sides of a right triangle whose hypotenuse corresponds to the apparent power. The cosine of the angle between the 

active power and the apparent power is the displacement power factor.

Figure 4: Vector addition of active and reactive power

1.4  Compensating and Controlling Reactive Power with Sunny Tripower

Compensating Reactive Power Demand with Q on Demand 24/7

Leading or lagging loads (e.g. cables, transformers) require reactive power. Transporting reactive power from the power 

plant to the load places a burden on the utility grid. It therefore makes sense to install a compensation system that provides 

reactive power at sites with many leading or lagging loads. In order to ensure the stability of the utility grid, grid operators 

require energy producers to take part in the compensation of reactive power. A PV system can complement or replace 

such a compensation system. 
Due to their design, large PV farms have a certain demand for reactive power which can be compensated with 

Sunny Tripower inverters. At the same time, Sunny Tripower inverters can feed reactive power into the utility grid. 

Compensation can take place both in feed-in and non-feed-in operation by using the Q on Demand 24/7 function.  

Using this function, the Sunny Tripower inverter provides reactive power for the PV farm equipment without placing a 

burden on the utility grid.

Controlling the Q(V) Characteristic Curve with Integrated Plant Control

The Sunny Tripower inverter can provide reactive power to the utility grid with the Integrated Plant Control function.  

The grid operator specifies the preferred process by which the inverter should supply reactive power to the utility grid.  

In many cases, the grid operator will require control in accordance with a Q(V) characteristic curve. 
SMA inverters with Integrated Plant Control are capable of representing this Q(V) characteristic curve without performing 

any measurement at the grid-connection point. The inverter can automatically compensate equipment installed between 

the inverter and the grid-connection point.
The function "Integrated Plant Control" is not capable of compensating irregular or fluctuating reactive power demands 

— e.g. from connected machinery — when the machinery is connected between the inverters and the grid-connection point. 

If the machinery is connected directly at the grid-connection point, it is possible to dynamically determine the reactive 

power demand of the machines using additional measurement equipment and then to provide this value as an offset to 

the Q(V) control.

Содержание STP 12000TL-US-10

Страница 1: ...functions are available Device type Reactive power provision 0 overexcited to 0 underexcited Q on Demand 24 7 Integrated Plant Control STP 15000TL 10 STP 17000TL 10 from firmware version 2 60 02 from...

Страница 2: ...er does not do any work and is therefore referred to as reactive power The time delay between the current and voltage curve its so called phase shift is a value which is easy to measure and characteri...

Страница 3: ...n as pure reactive power Q unit Var from the French volt amp re r actif which moves back and forth in the cables Figure 2 Pure reactive power current and voltage are phase shifted by 90 1 3 Apparent P...

Страница 4: ...compensated with Sunny Tripower inverters At the same time Sunny Tripower inverters can feed reactive power into the utility grid Compensation can take place both in feed in and non feed in operation...

Страница 5: ...ansformers switching equipment etc has an influence on the characteristic curve of the PV power plant as a whole Figure 5 Example of a Q V specified by the grid operators This is why the central PV fa...

Страница 6: ...ction point fast data transmission and installation and commissioning Grid friendly adherence to the characteristics desired by the grid operator even in the presence of very rapid changes in grid vol...

Страница 7: ...length MV Transformer Nominal apparent power SN Impedance voltage vk Impedance loss in case of short circuit at nominal power Psc 3 2 Entering Key Values in Sunny Design You can find a detailed manua...

Страница 8: ...rmer are activated in the area Configuration 10 Enter the key values for the cables used in the tabs Lines LV1 Lines LV2 and Lines LV3 11 In the tab MV transformer enter the key values for the MV tran...

Страница 9: ...or software and log in as Installer or User 2 If required enter the SMA Grid Guard code 3 Select and set the required parameter 4 Save settings Parameter name for BLUETOOTH or Speedwire Webconnect Par...

Страница 10: ...type and serial number PV system Impedance compensation Nominal apparent power of all inverters kVA Ohmic resistance for impedance compensation Lagging resistance for impedance compensation Leading r...

Страница 11: ...ivate only the function Q on Demand 24 7 The general setting of the grid management service e g cos phi setpoint or Q V characteristic curve can be set independently of function Q on Demand 24 7 using...

Отзывы: