Signal
Terminal
X7 and X9
EIA/TIA 568B (8-conductor)
Insulated conductor color
not assigned
wh/bn
white/brown
not assigned
bn
brown/white or brown
Additionally required accessories (not included in scope of delivery):
☐ LSA+ insertion tool
Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live
components results in death or serious injury due to electric shock.
• Disconnect the inverter on the DC side (see inverter manual). Always observe the five safety
rules.
• Disconnect the DC sub-distribution (see the DC sub-distribution manual). Always observe the
five safety rules.
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area
(see the manual of the respective DC sub-distribution). Always observe the five safety rules.
Property damage due to dust intrusion and moisture penetration
Excessively large or redundant holes in the membranes of the cable feed-through plate can cause
dust or moisture to penetrate the DC subdistribution.
• Only pierce as many holes in the membrane as you need for the cables.
• The hole in the membrane must be smaller than the diameter of the cable to be led through.
Damage to the assembly due to the use of unsuitable tools
The use of unsuitable tools can lead to the damage of the assembly.
• Only use a LSA+ insertion tool for the connection of the Ethernet cable.
Procedure:
1. Disconnect the inverter on the DC side (see inverter manual).
2. Disconnect the SMA String-Monitor (see SMA String-Monitor manual).
3. Disassemble the protective covers in the SMA String-Monitor.
4 Installation
SMA Solar Technology AG
Installation Manual
SSMAbleitKomm-IA-xx-11
26
ENGLISH
Содержание SSM-U-COMOVP
Страница 108: ...1 1 1 SSM U COMOVP Ethernet SMA String Monitor 1 2 1 3 1 SMA Solar Technology AG SSMAbleitKomm IA xx 11 108...
Страница 110: ...2 2 DC DC DC DC DC 5 3 22 3 SMA Solar Technology AG SSMAbleitKomm IA xx 11 110...
Страница 112: ...F DC G 230 VAC H 4 SMA Solar Technology AG SSMAbleitKomm IA xx 11 112...
Страница 113: ...4 2 24 SMA String Monitor SSM U XX10 A B C 4 SMA Solar Technology AG 113 SSMAbleitKomm IA xx 11...
Страница 123: ...1 1 1 SSM U COMOVP SMA String Monitor 1 2 1 3 1 SMA Solar Technology AG 123 SSMAbleitKomm IA xx 11...
Страница 125: ...3 25 A 1 2 B 1 RJ 45 C 1 RJ45 D 1 E 1 F 1 3 SMA Solar Technology AG 125 SSMAbleitKomm IA xx 11...
Страница 127: ...4 2 27 SMA String Monitor SSM U XX10 A B C D E 4 SMA Solar Technology AG 127 SSMAbleitKomm IA xx 11...
Страница 135: ......
Страница 136: ...SMA Solar Technology www SMA Solar com...