10 Technical Data
SMA Solar Technology AG
Installation Manual
SBxx-1SP-US-40-IA-xx-15
69
SB6.0-1SP-US-40
SB7.0-1SP-US-40
SB7.7-1SP-US-40
Range of the displace-
ment power factor (ad-
justable)
0.8
overexcited
to
0.8
underexcited
0.8
overexcited
to
0.8
underexcited
0.8
overexcited
to
0.8
underexcited
Feed-in phases
1
1
1
Phase connection
2
2
2
Overvoltage category
in accordance with
UL 1741
IV
IV
IV
Efficiency
SB6.0-1SP-US-40
SB7.0-1SP-US-40
SB7.7-1SP-US-40
Maximum efficiency at
208 V, η
max
97.2 %
97.1 %
97.1 %
CEC efficiency at 208
V, η
CEC
96.5 %
96.5 %
96.5 %
Maximum efficiency at
240 V, η
max
97.6 %
97.5 %
97.5 %
CEC efficiency at 240
V, η
CEC
97.0 %
97.0 %
97.0 %
10.2 AC Output, Secure Power Supply Operation
Maximum AC power
2000 W
Nominal AC voltage
120 V
AC voltage range
109 V to 132 V
Maximum output current
16 A
Minimum load
1 W
10.3 Multifunction Relay
Maximum DC switching voltage
30 V
Maximum AC switching current
1.0 A
Maximum DC switching current
1.0 A
Minimum load
0.1 W
Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with*
100000 switching cycles
* Corresponds to 20 years at 12 switching operations per day