6 Electrical Connection
SMA Solar Technology AG
Installation Manual
SBxx-1SP-US-40-IA-xx-15
34
13.
Connection of conductors of finely stranded wire
To connect conductors made of finely stranded wire, each terminal point must be opened.
• First insert the connector into the terminal point all the way to the lock (round
opening). Then insert a flat-blade screwdriver (blade: 4 mm (
5
/
32
in)) as far as it can
go into the actuation shaft (rectangular opening). Hereby the lock opens and the
conductor can be placed into the terminal point as far as possible. After the
connection has been made, the flat-blade screwdriver must be pulled out of the
actuation shaft.
14.
WARNING
Fire hazard due to faulty conductor connection
If the conductors are inserted into the actuation shafts (right-angled openings), a fire may
occur during inverter commissioning.
15. Connect the conductors to the terminal block for the AC connection:
• If there is a neutral conductor, connect the
neutral conductor to the terminal block in
accordance with the labeling. Insert the
conductor into the corresponding terminal point
(round opening) up to the stop.
AC-out
SPS
L1
L2
N
• Connect L1 and L2 to the terminal block in accordance with the labeling. Insert each
conductor into the corresponding terminal point (round opening) up to the stop.
16. Ensure the conductors are plugged into the terminal
points (round openings) as far at is will go and not
into the actuation shafts (rectangular openings).
AC-out
SPS
L1
L2
N
AC-out
SPS
L1
L2
N
17. Ensure that the terminal points are allocated to the correct conductors.
18. Ensure that the conductors are plugged completely into the terminal points up to their
insulation.