12 Technical Data
SMA Solar Technology AG
Operating manual
MC-BOX-12-3-20-BE-en-13
44
12 Technical Data
Connection of loads
Number of terminals
1 x three-phase
Rated power
138 kW
Rated grid voltage between L and N
230 V
Rated grid voltage between L1 and L2
400 V
AC voltage range between L1 and N
172.5 V to 265 V
AC voltage range between L1 and L2
300 V to 433 V
Current at rated values
3 x 200 A
Terminals for connection N, L1, L2, L3
Spring-cage terminals
Maximum connectable conductor cross-section
150 mm²
Minimum connectable conductor cross-section
50 mm²
Fuse
LV/HRC 1
Maximum permitted fuse rating for
F102
200 A gG
Sunny Island Connection
Maximum number of Sunny Island inverters
12
Rated power of the Sunny Island inverters
72 kW
Rated operating voltage between L and N
230 W
Rated operating voltage between L1 and L2
400 W
Current at Sunny Island ratings
12 x 26 A
Unaffected short-circuit current / relative rated short-circuit current at the terminals
≤ 10 kA
Terminals for connection N, PE, L
Spring-cage terminals
Maximum connectable conductor cross-section
10 mm²
Minimum connectable conductor cross-section
0.5 mm²
Fuses
12 x circuit breaker C40 A
Maximum permitted rated current of the back-up fuse
40 A gG
Short-circuit current breaking capacity of the back-up fuse
≥25 kA
Forward current of the back-up fuse
≤ 10 kA
Generator connection
Number of terminals
1 x three-phase
Rated operating voltage between L and N
230 V