10 Troubleshooting
SMA Solar Technology AG
Operating manual
STP15-25TL-30-BE-en-17
66
4. Press the locking tabs on the fan toward the center
of the fan.
5. Carefully remove the fan from the inverter.
6. Release and remove the fan plug.
1
2
7.
NOTICE
Damage to the fan due to compressed air
• Clean the fan only with a soft brush, a paint brush, or a damp cloth.
8. After cleaning, insert the fan plug back into the pin
connector until it snaps into place.
9. Insert the fan into the inverter until it snaps into place.
10. Push the fan guard into the retainer until it snaps into place.
11. Clean the fan on the left-hand side of the enclosure (see Section 10.2.2 "Cleaning the Fan on
the Left-Hand Side of the Enclosure", page 66).
10.2.2 Cleaning the Fan on the Left-Hand Side of the Enclosure
1.
DANGER
Danger to life due to electric shock
• Disconnect the inverter from all voltage sources (see Section 11 "Disconnecting the
Inverter from Voltage Sources", page 76).
2. Remove the ventilation grids on the left-hand and right-hand sides and clean them: