SMA Solar Technology AG
6 Electrical Connection
Operating Manual
GRID-BOX-12-3-20-BE-en-11
17
6 Electrical Connection
6.1 Overview of the Connection Area
6.1.1 Components and Terminals
Figure 8: Overview of the connection area
Position
Designation
Explanation
A
Terminals
X310
,
X311
with spring-cage
terminals
Spring-cage terminals for connecting the control cables
B
Surge arrester
The signal light on the surge arrester must be checked
regularly (see Section 10.2, page 29).
C
Terminals
X301:8-10
with spring-cage
terminals
L1
,
L2
and
L3
For connecting the Multicluster-Box line conductors
D
Terminal
X301:7
with spring-cage terminal
PE
For connecting the Multicluster-Box grounding conductor
E
Terminal
X301:6
with spring-cage terminal
N
For connecting the Multicluster-Box neutral conductor
F
Terminal
X301:5
with spring-cage terminal
N
For connecting the utility grid neutral conductor
G
Terminal
X301:4
with spring-cage terminal
PE
For connecting the utility grid grounding conductor
H
Terminals
X301:1
-
3
with spring-cage
terminals
L1
,
L2
and
L3
For connecting the utility grid line conductors