background image

7

TROUBLESHOOTING GUIDE

1. Valve does not function (red light does not flash when user  

    steps in front of sensor).

 A. No power is being supplied to sensor. Ensure that the main power is  
    turned “ON.” Check transformer, leads and connections. Repair or  
    replace as necessary.
B. EL-1500 sensor is not operating. Replace the EL-1500 sensor.

2. Valve does not function (red light flashes when user steps in  

    front of sensor).

A. Red light stops flashing when user steps away and valve makes a  
    “clicking” sound but does not flush.
    a. No water is being supplied to the valve. Make certain that the water  
        supply is turned “ON” and the Control Stop is open. No power is 
        being supplied to sensor. Ensure that the main power is turned “ON.”  
        Check transformer, leads and connections. Repair or replace  
        as necessary.
    b. EL-128-A cartridge is fouled or jammed. Turn electronic power to  
        valve “OFF” (failure to do so could result in damage to the solenoid  
        coil. Remove the solenoid operator from the valve and remove the  
        EL-128-A cartridge. Clean and/or repair as necessary.

B. The red light stops flashing when user steps away but the valve does  
    NOT make a “clicking” sound and does NOT flush.
     a.  EL-163-A solenoid shaft assembly is fouled or jammed. Turn electronic 
        power to valve “OFF” (failure to do so could result in damage to the 
        solenoid coil). Remove EL-101 or EL-166 nut from the solenoid 
        operator. Remove the coil from the solenoid operator. Use a spanner 
        wrench or pliers to remove the EL-163-A solenoid shaft assembly from 
        valve. Clean and/or replace as necessary. Be sure to replace plunger 
        spring when reassembling solenoid shaft assembly. 
C. The red light flashes three (3) short flashes, three (3) long flashes then 
    three (3) short flashes (“S-O-S”) and continues to repeat this cycle even 
    when user steps out of the sensor’s detection range.
    a. EL-1500 sensor wiring connections are incorrect. Re-wire sensor to 
       valve. One solenoid lead connects to the “TO VALVE” connection on 
       sensor. One transformer lead connects to the “24 VAC IN” connection 
       on sensor. Second solenoid lead and second transformer lead connect 
       together.
    b.  Wiring to sensor is ground shorted. Find short in wiring circuit and 
       correct.
    c. EL-165-2 solenoid coil is burnt out or coil is not connected to solenoid 
       plunger shaft. Reinstall or replace coil as necessary.

3.  Volume of water is insufficient to adequately siphon fixture.

A. Control stop is not open wide enough. Adjust control stop for desired  
    water delivery.
B.  Low consumption unit is installed on water saver or conventional fixture. 
    Replace diaphragm component parts of valve with kit that corresponds to 
    appropriate flush volume of fixture.
C.  Inadequate water volume or pressure available from supply. Increase 
    pressure or supply (flow rate) to the valve. Consult factory for assistance. 

4.  Length of flush is too long (long flushing) or valve fails to  

    shut off.

    

A.  Water saver valve is installed on low consumption fixture. Replace 

    diaphragm component parts of valve with kit that corresponds to  
    appropriate flush volume of fixture.

    B. Relief valve in diaphragm is not seated properly or bypass hole in  

    diaphragm is clogged. Disassemble inside diaphragm component parts 
    and wash parts thoroughly. Replace worn parts if necessary.

5.  Water splashes from fixture.

  A.  Supply flow rate is more than necessary. Adjust control stop to meet flow 

    rate required for proper cleansing of the fixture.

6. Leakage occuring at the push button.

  A.  Damaged or worn seals or lime build up in the actuator cartridge. Replace 

    with new HY-32-A cartridge.

7.  The flushometer does not flush or flushes only once and will not  

    flush a second time when the button is pushed.

  A.  The plunger is lodged in the actuator cartridge or the plunger by-pass  

    hole is clogged. Remove the actuator housing and cartridge from the  
    flushometer. Clean under running water. If cartridge parts are worn,  
    deteriorated or limed up and problem persists after cleaning, replace with  
    new HY-83-A cartridge.

      a. Turn off water at the control stop.
      b. Unscrew the housing coupling nut from the flushometer.
      c. Remove the actuator housing from the flushometer. The tubing  

        connections can be left intact.

      d. Remove the actuator cartridge from the flushometer body. Care should  

        be taken so that upon removal the actuator does not abruptly separate  
        due to spring compression within. If the actuator cartridge is lodged in  
        the body cavity, grip the exposed portion gently with a pair of channel- 
        lock pliers and rotate back and forth to loosen the o-ring seal.

      e. Separate the actuator housing to reveal the spring and plunger.
    B. Plastic tubing installed incorrectly. Install Plastic tubing correctly.

8.  The flushometer does not flush and a small amount of leakage 

    is visible below the valve.

  A.  Foreign material lodged in the cartridge. Remove the cartridge and inspect 

    for foreign material. Clean under running water.

  B. Damaged or worn seals or lime build up in the actuator cartridge. Replace 

    with new HY-32-A cartridge.

      a. Remove the button or actuator assembly from the wall or fixture.
      b. Disassemble the flange or button assembly from the actuator body.
      c. Unscrew the cartridge from the actuator body. 

NOTE: The metal  

       push button was designed to be vandal-proof and thus  
       requires removal from the wall for servicing.

  C. Plastic tubing installed incorrectly. Install Plastic Tubing Correctly.

When further assistance is required,  

please contact Sloan Technical Support at:

1-888-SLOAN-14 (1-888-756-2614)

NOTE: URINALS – When the sensor detects a user, a slow flashing red light appears in the sensor window. After eight (8) 

to ten (10) seconds, the light flashes rapidly to indicate that the sensor is armed. When the sensor no longer detects a 

user, the sensor immediately activates the solenoid valve after a 0.5 second delay.

WATER CLOSETS – Detection and activation are the same as for the urinal except when the sensor no longer detects an 

user, the sensor activates the solenoid valve after a three (3) second delay.

LAWS AND REGULATIONS PROHIBIT THE USE OF  

HIGHER FLUSHING VOLUMES THAN LISTED ON  

FIXTURE OR FLUSHOMETER.

!!! IMPORTANT !!!

Содержание 152 ES-S TMO SWB

Страница 1: ...ends only to persons or organizations who purchase Sloan Valve Company s products directly from Sloan Valve Company for purpose of resale This warranty does not cover the life of the batteries THERE A...

Страница 2: ...rred Mud Ring Orientation MUD RING Sloan A 50 Super Wrench Sloan A 109 Plier Wrench or smooth jawed spud wrench Wire stripper crimping tool 5 64 hex wrench supplied NEVER OPEN CONTROL STOP TO WHERE TH...

Страница 3: ...sh button actuator fittings and slide one nut onto each plastic tube Slide each plastic tube onto its corresponding push button actuator fitting and tighten tube fitting nuts F From behind wall slide...

Страница 4: ...TAILPIECE O RING TAILPIECE COUPLING FLUSHOMETER BODY CONTROL STOP C LOF SUPPLY C LOF FIXTURE 1 2 4 INSTALL FLUSHOMETER A Cut off excess plastic tubing so that there will be about 3 to 4 inches 72 to...

Страница 5: ...500 L GRD UNIT 1 UNIT 2 THRU 10 IF USED 120 VAC 24 VAC EL 1500 L SENSOR COIL WIRE 24 VAC COIL EL 1500 L SENSOR COIL WIRE 24 VAC COIL Wiring Diagram for Multiple Flush Valves 7 ELECTRICAL HOOK UP 8 INS...

Страница 6: ...a target Unless this target is a permanent fixture in the sensor s environment i e a wall or stall door it must be removed from the view of the sensor If this target is permanent the sensor will adap...

Страница 7: ...agm component parts of valve with kit that corresponds to appropriate flush volume of fixture B Relief valve in diaphragm is not seated properly or bypass hole in diaphragm is clogged Disassemble insi...

Страница 8: ...1 38 mm Vacuum Breaker Assembly RB Model 152 11 V 500 AA 19 mm Vacuum Breaker Assembly RB Model 192 Item Part Description No No 12A F 2 AT 1 38 mm Slip Joint Coupling Assembly RB Model 152 12B F 2 AW...

Отзывы: