CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PAGE

Ratings and Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:

Boiler Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Vent Requirements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Boiler Internal Baffles  . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Vent Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing Water trim  . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Installing Burner  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Oil Supply Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring the Boiler  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Operating Instructions:

Precautions Before Starting  . . . . . . . . . . . . . . . . . . . . . .6
Start-up  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning and Filling New Water Boiler  . . . . . . . . . . . . . .6
Wiring Diagrams  . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-11

Burner Data:

Riello  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Care and Maintenance:

Extended Shutdown  . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Oil Burner  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
General Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . .14

SAFETY WARNING:

KEEP BOILER AREA CLEAR AND FREE FROM 
COMBUSTIBLE MATERIALS, GASOLINE AND 
OTHER FLAMMABLE VAPORS AND LIQUIDS. 
FAILURE TO ADHERE TO ABOVE SAFETY
WARNING, MAY RESULT IN PERSONAL INJURY 
OR DEATH AND PROPERTY DAMAGE.

IMPORTANT:

The installation of this equipment must conform

to the requirements of the authority having jurisdiction or, in
the absence of such requirements, to the Installation of Oil
Burning Equipment, ANSI/NFPA 31, latest edition, and to the
National Electrical Code ANSI/NFPA 70, latest edition.  The
installation must also conform to the additional requirements in
this Slant/Fin Instruction Manual.  Where there is any differ-
ence, the more stringent requirement shall govern.

In addition, where required by the authority having jurisdiction,
the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, No. CSD-1, latest 
edition.

THIS MANUAL MUST BE LEFT WITH OWNER AND

SHOULD BE HUNG ON OR ADJACENT TO THE

BOILER FOR REFERENCE.

IMPORTANT:  This boiler must be installed by a trained, 
experienced, service technician, licensed for the installation
and servicing of oil burning equipment or otherwise qualified by
the authorities having jurisdiction over the installation.

Part No. 470908000  Publication No. EC-10DV-40 Rev.B

Printed in U.S.A. 1214

THIS BOILER OPERATES WITH POSITIVE PRESSURE IN
THE FLUE AND OVER FIRE, ALL SEALS MUST BE IN
PLACE WHEN OPERATING THE BOILER. ALL VENTING
MUST BE INSTALLED AND SEALED ACCORDING TO THE
VENT MANUFACTURER’S INSTRUCTIONS.

DIRECT VENT OIL-FIRED WATER BOILER/NO. 2 OIL

INSTALLATION AND OPERATING INSTRUCTIONS

EUTECTIC 

EC-10DV Series

CAUTION

The information in this manual must be followed exactly
to avoid personal injury, property damage or loss of life.

SEE BACK COVER FOR

SERVICE PERSONNEL

Содержание EUTECTIC EC-10DV Series

Страница 1: ...ditional requirements in this Slant Fin Instruction Manual Where there is any differ ence the more stringent requirement shall govern In addition where required by the authority having jurisdiction th...

Страница 2: ...usted to produce 13 CO2 All dimensions subject to normal manufacturing tolerance NOTE All boilers under 300 000 Btuh 87 9 kw input are tested and rated for capacity under the U S Department of Energy...

Страница 3: ...anticipated snow line The terminal shall be positioned so that flue gases are not directed where they can jeopardize people overheat combustible structures or enter buildings Vent terminal should be...

Страница 4: ...system causes the introduction of a frequent supply of fresh water into the boiler This will cause damage to the boiler Use of heat exchangers will prevent this damage PIPING FOR WATER UNITS NOTE On...

Страница 5: ...ld be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction INSTALLING THE BURNER See Burner Data pages 12 13 and Burner Manual supplied with b...

Страница 6: ...nt terminal and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE D...

Страница 7: ...EUTECTIC EC 10 DV 7 Aquastat Control and Honeywell R7184P Primary Single Zone Wiring for Beckett Carlin Burners Only...

Страница 8: ...8 EUTECTIC EC 10 DV...

Страница 9: ...EUTECTIC EC 10 DV 9...

Страница 10: ...EUTECTIC EC 10 DV 10 Honeywell L7248L Beckett 7600A and HydroLevel 3250 Controls See Adjusting Settings error codes for L7248L on page 11...

Страница 11: ...rting to default settings or has stopped running the Outdoor Reset algorithms The warnings are cleared when the issue s is resolved b To clear Err 8 condition depress and hold all three user keys simu...

Страница 12: ...lectrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligned with the correct index number 2 Retighten the retaining nut 1...

Страница 13: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Страница 14: ...roper burner operation ONLY THE NOZZLES SPECIFIED IN THIS MANUAL OR ON THE BURNER LABEL SHOULD BE USED FOR REPLACEMENT A flue brush triangular shape is supplied with boiler 7 Protect all of the firesi...

Страница 15: ...___________________________ Model _____________________________ Serial _____________________________ SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD...