Skytech: 3301P
REV. 2-7-12 Page 11
TIME OF DAY DISPLAY
1.
To check the current TIME of day, press the TIMER/TIME
button on the transmitter for less than 1 second. The current
TIME of day will appear in the TIME/TEMP frame replacing the
temperature reading.
2.
The TEMPERATURE will reappear in 15 seconds, or you can
press the SET button to cancel the display of the time.
DOWN
UP
MODE
SET
PROG
AHEAD
BACK
TIME
TIMER
COVER OPEN
Fig. 28 Time of Day
SETTING THE COUNTDOWN TIMER
This remote control can operate with the built-in, countdown timer
when the transmitter is in the ON or THERMO mode
(THERMO or
ON must be displayed on the LCD screen)
. DO NOT operate in
PROGRAM MODE, because time is pre-programmed into the trans-
mitter.
1.
Press the TIMER/TIME button on the transmitter for more than
2 seconds. The word TIMER and 0:15 flash on the LCD screen.
2.
Press the UP or DOWN button on the transmitter to begin
advancing through each of the countdown time options.
Available count down times are 15 min., 30 min, 45 min, 1 hr,
1 hr 30 min, 2 hr, 2 hr 30 min, and each additional half hour up to nine hours.
3.
To set the TIMER press the SET button on the transmitter. If the system is ON, it will remain on until the “timer” has
expired. If the system is in the THERMO mode, it will cancel ON and OFF, as the room temperature requires until the
“timer time” has expired.
4.
To cancel the TIMER operation, press the TIMER/TIME button for more than 2 seconds.
OPERATIONAL NOTE:
When the TIMER is used in the THERMO mode, the THERMO operation will be disabled until
the “countdown time” has expired, then normal THERMO mode will presume.
DOWN
UP
MODE
SET
PROG
AHEAD
BACK
TIME
TIMER
COVER OPEN
Fig. 29 Setting Timer
LOW BATTERY INDICATOR
The low battery icon will appear when battery power has dropped significantly. At
this time, approximately two weeks of battery power remains until the transmitter may
experience partial or complete loss of functions.
NOTE: A reversed battery can activate the LOW battery icon.
Fig. 30 Low Battery Icon
ADDITIONAL PROGRAMMING - OPTIONS TO CHANGE SWING TEMPERATURE
The thermo-transmitter operates the fireplace system whenever the ROOM TEMPERATURE varies a certain number of
degrees from the SET TEMPERATURE. This variation is called the “SWING” or TEMPERATURE DIFFERENTIAL. The
normal operating cycle of a fireplace system may be 2-4 times per hour depending on how well the room or home is insu-
lated from the cold or drafts. A smaller “swing number” increases the number of cycles so the room temperature is more
constant. A larger “swing number” decreases the number of cycles, which saves energy, in most cases. The factory set-
ting for the “swing number” is 2. This represents a temperature variation of +/- 2°F (1°C) between SET temperature and
ROOM temperature which determines when the fireplace will be activate. The “SWING” number values are:
1= +/- 1°F (.5°C), 2= +/- 2°F (1°C), 3 = +/-3°F (1.6°C).