SKYLUX Skycom CE MASTER Скачать руководство пользователя страница 8

E_MH_Installation_instruction_Skycom_Skymax_CE

01/10/2016

8/26

 

Connection, operation and settings

Motor (actuator)

The actuators must be connected to output terminals 2-3. The max. load is 5A.
It is possible to disable the line monitoring on the motor output. The cables can be connected in series or parallel or a 
combination of these (see drawings motor and electrical schemes). 
It is important to keep the right polarity. The motors of most systems must be connected via a limit switch - see electrical 
scheme of the specific opening system.
See table at the end for cable sections and max. motor cable length.

Cable monitoring (line monitoring) on the motor output

The control is equipped with 3 possible settings for cable monitoring (line monitoring), which can be configured by  
means of jumper J2. 
 

a. Jumper J2 mounted in pos. “Motor line” (Setting for Skylux

®

 160° CE, Skymax

®

 CE old and new and Cintramax

®

 CE)

Known motor: line monitoring (2-3) with double wired motor connexion.
Jumper J3 (actuator output) is set according to the number of termination resistors (27KΩ) to be detected – 1 to max. 4 
lines can be detected by moving jumper J3 – this means that the cable installation between the control unit and the motors 
can be established in series connection (cable connection from smoke hatch 1, further to smoke hatch 2, etc.), or parallel 
connection (cable connection from each smoke hatch to the control), or a combination of these. However, as mentioned 
max. 4 different lines can be detected, each of them connected to the end resistor of 27KΩ. 

Jumper description

J3

Number of connected 27Kohm terminal 
resistors for actuator output

J2

Chooses line monitoring through motor 
terminals 2-3 (Mot Mon) or separate 
wire terminals 1-3 (Ext Li Mon), or no 
line monitoring when J2/J3 is removed

F1

Fuse 8A for actuator output

Line 1

1

CH 

1

24V Out

Actuator

2

3

+

-

5

LIP 

2

1

4

6

3

M1

24V Out

Actuator

2

1

Actuator 

Motor line monitor 
Ext 3 wire monitor

(line 1)

Blue

Next LIP

Brown

Blue

J2

1

J3

4
3
2
1

M2

Blue

Brown

Содержание Skycom CE MASTER

Страница 1: ...Release 10 2016 SMOKE AND HEAT EXTRACTION CONTROL EN Skycom Skymax CE 24V 5A User manual and installation instructions ENGLISH...

Страница 2: ...gs p 5 General description p 6 Installation p 6 Connection operation and settings p 8 Motor actuator p 8 Fire switches p 10 External priority switch p 11 Smoke heat detectors p 12 Comfort ventilation...

Страница 3: ...n SHE systems are legally required in specific buildings In such buildings only CE certified systems in accordance with European and Belgian norms are allowed to be used At the same time our SHE syste...

Страница 4: ...s automatically SKYCOM MASTER Art nr 30975 with Skymax CE without positive safety does NOT open automatically Cable sections in function of the distance SKYCOM MASTER Art nr 30975 SKYCOM SLAVE Art nr...

Страница 5: ...e routes make sure the firemen can reach easily the fire place See to the possibility of a quick signal to the fire department in case of fire by a full fire detection system Consult your architect co...

Страница 6: ...ailable on outputs for con nection with other systems AFA systems Air gates buzzer in the building We advise to consult your fire department to choose the best installation place fort all SHE accessor...

Страница 7: ...DETECTOR COMFORT VENTILATION SMOKE AND HEAT SENSOR 1 2 3 4 6 5 7 4 x 0 5 mm 2 fireproof 6 x 0 5 mm 2 2 x 0 5 mm 2 3 x 0 5 mm 2 3 x 0 5 mm 2 standard standard fireproof fireproof Max 5m fireproof 2 x...

Страница 8: ...ramax CE Known motor line monitoring 2 3 with double wired motor connexion Jumper J3 actuator output is set according to the number of termination resistors 27K to be detected 1 to max 4 lines can be...

Страница 9: ...ng the red LED in the LIP must light This indicates that polarity of the actuator is correct Table of LIP settings SA Power LM Large parallel operation Jumper OPT mounted both motors stop at the same...

Страница 10: ...ast switch in order to establish the line monitoring correctly this can either be done by moving the factory mounted resistor from the terminal strip to the last fire switch or connect jumper J1 in th...

Страница 11: ...3 and open 1 4 outputs of the add on PCB and is indicated by LD3 and LD2 Therefore in the priority switch 10k resistors are integrated To avoid confusion there can be only one priority switch Informat...

Страница 12: ...pening time after that nothing happens Continuous up signal gives 3x10 sec 30 sec One press on down closes the actuator completely it takes 18s longer compared to fully closing time In order to avoid...

Страница 13: ...open 10 k Supplied with Panel Weather sensor Close all function Install the rain and wind detection as close as possible to the smoke hatch at a place where the wind speed is equal to the wind speed...

Страница 14: ...cription for control units connected with bus connection If more control units are connected by means of a bus connection the following are monitored communicated between the control units A detected...

Страница 15: ...close DIP 7 On the motor output opens shortly 3 seconds once a week and closes immediately after This function is used to give the right tension on the smoke vents to keep them airtight Function of h...

Страница 16: ...ire monitor line 1 Next LIP Brown Blue only la Red 2 5mm2 Batteries 2x 12V 7 2 Ah Black 2 5mm2 Potential free NO NC contacts Max 48V 0 5A PS1 Power Supply 180 250 VAC 24VDC 150W 200W Potmeter comfort...

Страница 17: ...Potmeter for comfort features OFF ON unted J9 7 J1 6 7 6 J1 7 6 ntrol or line ol point VT No 1 T 2 3 27k 13 14 10k 16 17 10k 1 3 10k 1 4 10k POWER OPEN CLOSE SVM addon 5 4 3 2 1 6 PRIOR CLOSE OPEN 1...

Страница 18: ...1 5mm 24VDC 1 2 3 4 limit switch LIP 2x1 52mm Fireproof Max 5m 5 6 M Blue Brown 7 8 M Blue Brown POWER OPEN CLOSE SVM addon 5 4 3 2 1 6 Priority switch Remove resistors when mounting priority switch C...

Страница 19: ...P 10 Bus comfort ON The control reacts on comfort signal via bus activity The control does not react on comfort signals via bus activity Always reaction on weather signal and failures via bus activity...

Страница 20: ...E_MH_Installation_instruction_Skycom_Skymax_CE 01 10 2016 20 26 FRONT PANEL LED s MASTER SLAVE BUTTONS MASTER ONLY RESET SKYMAX...

Страница 21: ...d connector keypad fail J9 Check settings arrows and connections according the schemes Yes Only close Blue lights when smoke vents are open flashes when the smoke hatch opens or closes Yes Yes lights...

Страница 22: ...or 2 x 0 5 mm Cable between control units bus 3 x 0 5 mm Priority switch 4 x 0 5 mm Supply for control 230VAC 3 x 1 5 mm Comfort ventilation button 3 x 0 5 mm Wind and rain sensor 3 x 0 5 mm Only to b...

Страница 23: ...is activated should not be carried out if the wind is more than 6 m sec as there might be a risk that the opening system cannot close automatically Control of the batteries If the batteries are replac...

Страница 24: ...ll versions until 2014 35370 Main board Skycom CE all versions from 2015 31786 Main Board Skycom CE Slave until 2014 until stock lasts 31783 Power supply 230 VAC 28 5 VDC 8A 31784 Circuit breaker 10A...

Страница 25: ...numbers of items to which this declaration relates is in conformity with the following standard s or other normative document s EN12101 10 2006 EN61000 6 2 2005 EN61000 6 4 2001 EN61000 3 2 2005 EN61...

Страница 26: ...integrates most functions Max 35 controls in the same bus connection Alarm output Potential free SPDT change over max 48V 0 5A Fault output Potential free SPDT change over max 48V 0 5A Supply output 2...

Отзывы: