E_MH_Installation_instruction_Skycom_Skymax_CE
01/10/2016
26/26
Power supply
: 230V AC / max. 1,2A
Operating conditions
: - 5 °C to + 60 °C / Humidity max 90%, non- condensing/
internal use without aggressive vapers & gases
Protection degree
: IP54
Colour
: RAL 9003 (white)
Dimensions WxHxD
: 286x238x113 mm
Weight incl. batteries
: 7,5 kg
Autonomy battery
: Min. 72 hours
Internal T-sensor
: Alarm generated at 75°C
Max. load
: 24V / 5A (Fuse F1: 8A Fast acting)
Motor output
: 1 pc. (terminals 6mm²) – line detection: 1-4 lines
Fire switches & zones *
: 1 fire zone, 8 - 10 pcs. external fire switches,
depending on the load
Comfort zones *
: 1 comfort zone - unlimited number of switches
Smoke- and heat detectors
: 1 input - max. 20 pcs. detectors per control
Priority switch
: 1 input for an external Priority switch
Wind- and rain sensor *
: Input for close all
Connection of control units
: Bus connection integrates most functions -
Max. 35 controls in the same bus connection
Alarm output *
: Potential free SPDT change over max. 48V 0,5A
Fault output *
: Potential free SPDT change over max. 48V 0,5A
Supply output *
: 24VDC 0,5A at 230VAC operation
Line surveillance on
: Motor lines, fire switches,smoke detector Priority switch,
and communication bus
Visual indication (LED)
: OK, AC fault, Low battery, Line fault, Alarm, comfort open
*
not present on Slave
Manufacturer:
AG.PLASTICS, Spinnerijstraat 100, B-8230 Harelbeke, Belgium, website: www.skylux.be
SHE service: Tel.: +32 (0) 56 24 81 05 I e-mail: [email protected]
Skycom Skymax CE Control:
Skycom CE Manual:
Version
Production date
Description
01
June 2014
First release
02
March 2015
New PCB with low consumption, keypad, J9, J11, T-sensor, ...
03
October 2016
EMC update: f GND 22-G+SW
Version
Release date
Description
01
December 2015
First release
02
October 2016
New wind and rain detector AWR-24/250 added
SHE survey added + EMC update
TECHNICAL SPECIFICATIONS
CONTROL FOR 1 FIRE ZONE AND 1 COMFORT ZONE
REVISIONS