Load graphs

 General considerations

The following pages contain the load graphs for the Climalux profile system. You can use these to determine the 

free span of the gutter profiles and the supports in relation to the prescribed load.

A distinction is made between Climalux roofs with plastic sheets (pages 78 & 79) and Climalux roofs with single 

and double glazing (pages 80 & 81).

The maximum allowable bending is 1/200 (= 1 cm per 200 cm free span) with plastic sheets.

This includes the weight of the structure and the plastic sheets. Select the graph in relation to 

the prescribed snow 

and wind load. This depends on the region and the orientation.

The maximum allowable bending is 1/300 (= 1 cm per 300 cm free span) with single glazing.

This is including the weight of the structure. In order to determine the total load, add 

the weight of the glazing to 

the prescribed snow and wind load. To determine the weight of the glazing, calculate 2.5 kg per m² and per mm 

thickness. Example: single glazing with a thickness of 8 mm weighs 8 x 2.5 = 20 kg/m². After converting into N/

m² x factor 9.81, this results in 20 x 9.81 = 196.20 N/m². Suppose the prescribed snow and wind load is 500N/m² 

and the glazing is 200 N/m², the total load would be approximately 700 N/m². In order to limit the weight of the 

glazing, the axis distance between the support profiles (AX) is limited to a maximum of 750 mm. The total width of 

the roof is divided into equal parts. 

The bending of 1/200 of 1/300 is achieved with a maximum load. For example, a gutter support of 5000 mm with 

a maximum bending of 1/300 will bend 16.6 mm when loaded. Less if unloaded

These graphs do not apply with regard to a continuous support or a structure under the gutter profiles installed by 

the customer.

The gutter profiles may put pressure on supporting window profiles when installed on top of each other.  

A possible bending of the gutter profile above the sliding doors should, therefore, be taken into account.

When the selected gutter (support) cannot be installed where a certain span or load is concerned, select a gutter 

support that can handle a larger span. You could also install an extra post to decrease the free span.

“Span” refers to the distance between the posts. The total width of the roof = the free span + the width of the 

posts.

The roof’s supporting posts should always be located at the corners of the roof. We do not recommend moving 

the post supports inwards.

Any sun blind installed on the profiles are at your own risk and should be included in the calculation as an additional 

load.

In case of large spans or loads, the use of reinforcement profiles is recommended. These are slid into the 

aluminium profiles. The reinforced profiles V822 and V14105 are not supplied. These can be bought at any local 

hardware store. We recommend treating the reinforcement profiles with an anti-corrosion product.

The selection of required fixing material is dependent on the foundation or the walls. Check whether the 

foundation and the walls on which the structure is to be anchored have a sufficient load-bearing capacity. The 

installer is responsible for the assessment of the appropriate fixing materials for the load and basis on which the 

structure is to be fixed. Please contact your fixing material supplier or specialised engineering consultants in case 

of doubts. Skylux cannot be held liable for the installation or the fixing material used.

We recommend removing any snow from the roof to prevent accumulation against the wall by the wind. When 

snow on a higher roof can slide on to the Climalux roof, measures must be taken to prevent this, for example, by 

using snow hooks and snow beams.

You can use the Climafast calculation application to select the correct profiles and support in relation to the 

dimensions of the Climalux roof, the prescribed load and the glazing.

The latest version of this calculation application can always be downloaded from www.skylux.be.

Содержание Climalux 36179

Страница 1: ...CANOPY Climalux Mounting instructions EN Art N 36179...

Страница 2: ...AN OF CLIMALUX CONSERVATORY ROOF p 11 SPECIFIC INSTALLATION TIPS FOR THE CLIMALUX SYSTEM p 12 29 POSTS p 13 GUTTER p 14 16 GUTTER RAFTER FOR ROOF WITH OVERHANG p 17 18 WALL PROFILE p 19 RAFTERS AND SI...

Страница 3: ...R L16P SIDE PROFILE 16 MM CL16 CLIP ALU 16 MM CLLX SIDE CLIP 16 MM CLSB BASE SCREWABLE CLIP FROM 7 UP TO 16 MM CLST TOP SCREWABLE CLIP CLSL TOP SCREWABLE SIDECLIP PX POST 110 141 FOR GUTTER GX PGDX PO...

Страница 4: ...IECE GUTTER FOR GX GLX GRSX END PIECE GUTTER FOR GX GR LOGO LOGO CLIMALUX FOR END PIECE GUTTER GDSX END PIECE FOR CROSS BEAM GDX MSX END PIECE WALL PROFILE FOR MX 909 CONNECTING PINS LGDX FIXING PROFI...

Страница 5: ...ted as a claim Terms conditions and guarantee The guarantee is void when the installation instructions provided below are not followed Not following the instructions and or using other parts may have...

Страница 6: ...m for a Climalux For a construction with eave please consult page 22 Determine the width B fig 2 page 7 The width B of the Climalux is the distance between the outer side of the side rafters If the Cl...

Страница 7: ...e slid through the slotted holes in order to position the base plate properly The U for the base plate can be moved 20 mm either way to allow proper adjustment The 3 4 5 rule Determine the auxiliary p...

Страница 8: ...the walls Make a slot in the walls against which the conservatory roof is to be installed Install a lead slab or zinc flashing Height first joint above Hm h and max 60 mm above the wall profile LED l...

Страница 9: ...mm sheet must have a clearance lengthwise of 1 5 cm u Never block the sheet lengthwise or widthwise Always ensure sufficient clearance u Never stick the sheet using silicone even when it does not dam...

Страница 10: ...lating struc ture in the sheet are sensitive to foot knee and other impressions at the surface Please take enough precau tions during transport and installa tion Impressions in the sheet are not cover...

Страница 11: ...ns_Skylux_Climalux Overview drawing of the conservatory roof A10 A11 posts page 13 29 A20 A23 gutters page 14 18 29 A30 A33 wall profiles page 19 29 A40 A42 rafters side rafters page 20 28 A10 A11 A20...

Страница 12: ...E_MH_Mounting_instructions_Skylux_Climalux 01 11 2017 12 36 Climalux Installation tips...

Страница 13: ...rew set fig B for the corner posts Determine the position of the PV base plates as indicated on page 7 and anchor these on a solid foundation in concrete using the suitable fixing accessories not supp...

Страница 14: ...be installed between two walls The 5 mm clearance on each side is required for the installation of the slide ends Pre drilling is required to install the U brackets if the gutter rafter is reinforced...

Страница 15: ...Use a 80 mm circular drill not supplied Slide in the reinforcement profile V822 optional Installation of the U bracket PU Use the post caliber for the correct positioning The reinforcement profile V8...

Страница 16: ...909 A raised profile GR can be installed on the GX gutter Position the side gutter slide ends first and subsequently fasten the GR profile on to the gutter every 500 mm 500 GR Install the water outlet...

Страница 17: ...14105 is not supplied It can be bought at any local hardware store We recommend treating the reinforcement profiles with an anti corrosion product 117 190 100 140 GDX GDCX V14105 Installation of the U...

Страница 18: ...d screws ZSG Multiple gutter elements can be connected to each other for gutter lengths 7 m A gutter support must be installed at every gutter connection point The gutter profiles can be linked using...

Страница 19: ...at the top indication line with a diameter in function of the chosen fixing material Drill also a hole every 500 mm in the bottom indication line and start at 30 mm from the edge Important Slight the...

Страница 20: ...raphs on page 31 or calculate using the Climafast calculation application at disposal for free for professionals Components Rafter DX C3 or CY10 The rafters DX are pre cut to size Preparation Fix the...

Страница 21: ...lastics can be found on page 9 10 Divide the total width in equal parts of maximum 750 mm for glass The glazing quantity is determined as following B 60 mm 750 rounded off upwards The width of the gla...

Страница 22: ...he rafter DX rests on the gutter rafter GDX at the gutter side Every rafter is fastened with 2 fixing profiles LGDX and ZSG screws Every rafter is fastened on to the wall side with 1 lacquered ZSG scr...

Страница 23: ...Climalux Spacers Preparation spacers AX Fix a sealant C3 8 11 and 16 mm or CY10 8 9 mm on every spacer Installation spacers AX A spacer AX is clipsed between the rafter profiles at the gutter and wall...

Страница 24: ...protected side of the sheet is always upwards All useful information for the processing and installation of glazing plastics can be found on page 9 10 Apply a silicone sealant that does not affect pla...

Страница 25: ...are 3 positions for the clips Position 1 for glass 44 2 thickness 8 9 mm Position 2 for glass 55 2 thickness 10 11 mm Position 3 for 16 mm synthetic sheets The clips are fastened manually using a rubb...

Страница 26: ...nds Fasten the CLSB to the rafter DX using ZSB screws Fasten perpendicularly and use a slight torque to ensure the screw head is pressed flat against the CLSB The CLST clips must be fastened manually...

Страница 27: ...L16P profile against the outside against the rafter If you work with VRIJSTAAND or against the wall fasten the L16P profile every metre laterally against the rafter with ZSG or against the wall CLIP F...

Страница 28: ...pressed flat against the CLSB Cut the CLLX CLSL profile obliquely in accordance with the roof slope x at the wall side To determine the length of the CLLX CLSL profile measure the distance to the stop...

Страница 29: ...red screws ZSG We recommend to pre drill with 3 4 mm to avoid lacquer damage A frontal UGS water outlet is required to ensure that the water can flow outside when the water drainage is obstructed if t...

Страница 30: ...p of each other A possible bending of the gutter profile above the sliding doors should therefore be taken into account When the selected gutter support cannot be installed where a certain span or loa...

Страница 31: ...to the snow and wind load Practical example The axis distance AX between the rafters is 1000 mm for plastic sheets with a width of 980 mm The depth D of the roof is 3500 mm Determine the point on the...

Страница 32: ...options Either you select the gutter GX with reinforcement V822 which allows a free span of 4100 mm Or you select a gutter rafter GX for maximum span of 3645 mm You then have to install an extra post...

Страница 33: ...d is 500 N m 50 kg m The glass weighs 25 kg m ca 250 N m The total weight is 750 N m Determine the point in the 750 N m 1 300 graph and select a gutter support above this point The graph now has two o...

Страница 34: ...former per LED strip of maximum 7 meters Pull the extenstion cable 6 m through the lateral rafter of the wall profile to the gutter The transformer is placed in the wall profile for which there is som...

Страница 35: ...op profile 7 mm CY10 ZSB CY10 S16X 8 mm CY10 ZSB CY10 S16X 9 mm CY10 ZSB CY10 S16X 10 mm S16X 11 mm S16X 12 mm ZSG S16X 13 mm ZSG S16X 14 mm ZSG S16X 15 mm ZSB ZSG S16X 16 mm ZSB S16X Key ideal soluti...

Страница 36: ...017 ONLY USE ORIGINAL PARTS DELIVERED BY SKYLUX EVERY GUARANTEE IS CANCELLED IF NON ORIGINAL PARTS ARE USED SKYLUX IS A REGISTERED BRAND OF SKYLUX SPINNERIJSTRAAT 100 B 8530 STASEGEM T 32 0 56 20 00 0...

Отзывы: