4 Climate
4.1 Central air intake
The central air intake function is used to adjust the temperature of the fresh air before it enters the sections. The
air is taken into an air mixing room where it may be heated up or cooled down.
Cooling
Outside temperature sensor
Temperature sensor
Humidity
sensor
Figure 1: House with central air intake from air mixing room for adjusting the temperature of outdoor air
Press
Central air intake | Temperature
Cooling temperature
Setting for the inside temperature that activates the cooling.
It is set as an absolute temperature but also functions as an offset for the
Air in-
take setpoint
. It means that the Cooling setpoint changes accordingly when the
Air intake setpoint
is adjusted.
Air intake setpoint
Setting for the inside temperature that activates the ventilation.
To increase the
Air intake setpoint
without increasing the heating/cooling temper-
ature, you must adjust
Cooling setpoint
/
Heating setpoint
with the corresponding
number of degrees after you have adjusted the
Air intake setpoint
.
Heating setpoint
Setting for the inside temperature that activates the heating.
It is set as an absolute temperature but also functions as an offset for the
Air in-
take setpoint
. It means that the
Heating setpoint
changes accordingly when the
Air intake setpoint is adjusted.
Outside temperature
Display of the current outside temperature.
Air intake temperature
View of the temperature at which air inlets are regulated.
Air intake sensor 1
View of the current temperatures of the individual sensors.
Up to four temperature sensors can be connected. The controller will regulate the
temperature in relation to an average of their registrations.
Press
Central air intake | Heating
Heating active
Connection and disconnection of heat supply.