DOL 31 Speed Controller
Technical User Guide
25
8 Settings
8.1 Factory settings
DOL 31 has following default setup.
Menu item
Minimum
Default settings
Maximum
Daily User Menu
Temperature
0 °C
20 °C
40 °C
Mode
-
Automatic - Slave
-
Minimum AC output
0 VRMS = 0 %
60 VRMS = 26 %
150 VRMS = 50 %
Maximum AC output
150 VRMS = 50 % *
230 VRMS = 100 % *
230 VRMS = 100 % *
Service menu
Temperature alarm offset
±1 °C
±4 °C
±20 °C
Control temperature offset
- 10 °C
- 10 °C
+ 10 °C
P band
2 °C
4 °C
10 °C
Minimum DC output
0 V
0 V
10 V
Maximum DC output
0 V
10 V
10 V
Input
-
0-10 V
-
Temperature scale
-
Celsius
-
Safety mode
-
Yes
-
Invert
-
No
-
Language
-
English
-
*Depending on the actual supply voltage.
8.2 Functions in menu mode
Function
Automatic Master
mode
Automatic Slave
mode
Manual mode
DOL 12
X
0 10 V input signal
X
0-10 V or 10-0 V analog output
signal
X
X
X
Temperature alarm
X
Control temperature
X
Control relay
X
P band
X
Invert
X
X
Safety mode
X
Turn off limit
X
Minimum AC output
X
X
X
Maximum AC output
X
X
Alarm relay
X
X
X