DA 600 LPC • DA 600 • ECT 632-6 • DCT 632-6
Technical User Guide
57
7.2 DA 600
445085
DA 600-7F-2
445099
DA 600-7-2
445098
DA 600-7-2
445090
DA 600-7-2
Electrical
Rated voltage
V AC
1x230 ± 10%
3x200 -5 % +10 / 3x230 ± 10 %
3x400 ± 10%
Operating voltage
V AC
207 – 253
190 – 253
360 – 440
RCD
To be installed
in accordance
with applicable
laws and stan-
dards. RCD 300
mA (type B)
may be used in
front of the sup-
ply voltage for
DOL 38-2 regu-
lated fans
-
Frequency
Hz
50
60
50
Leakage current to ground
mA
Max. 2.5
Pay attention to
other leakage
current sources
in the house
-
Max. ballast fuse
A
16
-
Max. power consumption
At 200 V AC
A
-
3.87
2.92
-
Max. power consumption
At 230 V AC
A
4.86
3.86
2.72
-
Max. power consumption
At 400 V AC
A
-
-
-
2.07
Max. input power (P1)
W
1115
1096
833
1125
Max. power (P2) shaft
W
-
1100
730
730
Efficiency motor [η]
%
-
84.1
80.5
80.5
CosPhi [Φ]
Factor
-
0.74
0.71
0.71
Regulation ability
Frequency
ON/OFF
ON/OFF
ON/OFF
Motor protection
DOL 38-2
TP 211
TP 211
TP 211
Mechanical
Cable length
m
1.5
Min. duct diameter
mm
636
The diameter of the fan
blade
mm
625
Number of fan blades
pcs.
3
Fan blade pitch
°
Periferi 25 / Nav 45
Fan output
Revolutions (rated current)
per minute
RPM
1390-1410
1390-1410
1390-1410
1390-1410
Air output at 0 Pa
m
3
/h
16400
15400
15100
16700