DA 820 LPC -3
Technical User Guide
47
7 Technical data
7.1 DA 820 LPC -3 1x230 V
445126/445136
DA 820 LPC-10-3
445128/445139
DA 820 LPC-12-3
Electrical
Rated voltage
V AC
230 ± 10 %
Operating voltage
V AC
180 – 253
For supply voltages below the rated voltage range, a reduction of the
fan’s RPM may occur depending on the load and ambient tempera-
ture.
RCD
To be installed in accordance with applicable laws and standards.
RCD 300 mA (type B) may be used in front of the supply voltage for
LPC regulated fans.
Frequency
Hz
50/60
Leakage current to ground
mA
Max. 9.10
Pay attention to other leakage current sources in the house.
Max. ballast fuse
A
16
Max. current consumption
At 230 V AC supply
A
5.99
9.86
Max. input power (P1)
W
876
1462
CosPhi [Φ]
Factor
0.63
Regulation ability
10 to 100% / 9 - 0 V
Motor protection
Built-in current limiter in LPC motor control.
Use fuse in front of LPC motor control.
Thermal cutout (PTO)
445126, 445136
-
Thermal cutout (PTO)
445128, 445139
Thermik S01.120.05 Separate cable
Interface
Inputs
A1: Analog fan speed
V DC
10 – 0 (default)
D1: Start / Stop
V DC
0 / 24 with internal pull-up
D3: Reversal
V DC
0 - 24 with internal pull-up
R1: Alarm relay
1 A, 30 V DC, 24 V AC
Mechanical
Cable length
m
2 shielded
Min. duct diameter
mm
820
The diameter of the fan
blade
mm
800
Number of fan blades
pcs.
3
Fan blade pitch
°
50
Fan output
Revolutions (rated current)
per minute
RPM
1000
1170
Air output at 0 Pa
m
3
/h
24300
29000
Содержание 445126
Страница 2: ......
Страница 25: ...DA 820 LPC 3 Technical User Guide 25 4 7 2 DA 820 LPC 3 4 7 2 1 Cable plan 4 7 2 2 Terminals in LPC 230 V fan...
Страница 39: ...DA 820 LPC 3 Technical User Guide 39 4 7 9 DA 820 LPC 3 DA 74CV stepless with reverse 4 7 9 1 Cable plan...
Страница 41: ...DA 820 LPC 3 Technical User Guide 41 4 7 10 DA 820 LPC DA 74CV stepless with alarm relay 4 7 10 1 Cable plan...
Страница 54: ......
Страница 55: ......