6.1 Resetting errors
When the motor controller stops and an error message is displayed, it can be reset in one of the following ways:
• Disconnect the supply voltage for 10 minutes. Reconnect the supply voltage.
• Press the stop button on the motor controller.
0-1
Pres stop.
StoP
Display shows
StoP
.
By error
O-I
,
hO-I
or
I_t-trp
there is a time delay to prevent the damages that may occur by repeatedly activat-
ing the motor controller to an error condition.
The time delays is according to the below table.
Error
Time delay before reset is possible
1
2 seconds
2
4 seconds
3
8 seconds
4
16 seconds
5
32 seconds
6 ≤
64 seconds