SKOPE MISA Cool & Freezer Rooms
Installation
Installation Manual
Drop-In Refrigeration Unit
The following information applies to SKOPE MISA Drop-In refrigeration
units. For information on SKOPE MISA Freeblock refrigeration unit
installation refer to “Freeblock Refrigeration Unit” on page 20. If the room is
supplied with a third party drop-in unit or remote refrigeration system, refer
to the documentation provided with the drop-in or remote refrigeration unit
for further information.
Safety
When installing, using, maintaining or servicing the Drop-In refrigeration
unit, follow the safety and service guidelines on page 18.
Installation
The SKOPE MISA Drop-In refrigeration unit is designed to be located on top
of the cool/freezer room. Follow the instructions supplied with the Drop-In
refrigeration unit. Once installed, have the Drop-In refrigeration unit
commissioned by a licenced technician before initial start-up.
Drainage
Although the unit has its own condensation tray, high heat and humidity may
cause the tray to overflow. To compensate for this the Drop-In refrigeration
unit must be installed with a drain connection to a waste outlet.
Ventilation
There must be adequate ventilation and airflow around the Drop-In
refrigeration unit. Poor ventilation will void the warranty. The unit condensing
temperature must not exceed 45°C. If adequate airflow is not available,
mechanical air extraction must be used. Mechanical extraction of condenser
air into ceiling space or preferably out of the building is advised.
Enclosures
If the Drop-In refrigeration unit is enclosed, the enclosure must have an air
intake grille and the ceiling above must have adequate extraction to the
outside of the building. This must be in place prior to room installation and
should be done based on the installer recommendations. This work is not
the responsibility of SKOPE or the SKOPE approved installer.
Power Supply
We recommend that single-phase Freeblock refrigeration units are hard
wired to a 20 Amp circuit with isolation switch, and that 3-phase Freeblock
units are connected to a suitable circuit as required as specified on the unit
rating label. Refer to “Electrics” on page 25 for more information.
Refer to the rating label for power supply requirements. The rating label is
located either on the cabinet interior or on the Freeblock refrigeration unit.
Controller
The electronic controller control panel should be located beside the room
door.
Lighting
If the unit is fitted with a light, the light must be disconnected or removed.
Refer to “Compliance Kit” on page 25 for room lighting requirements.