25
SKOPE MISA Cool & Freezer Rooms
Installation
Installation Manual
Electrics
All electrical wiring should be completed by a licenced electrician and
installed in accordance with the relevant electrical wiring rules and
regulations (AS/NZS 3000).
Compliance Kit
A compliance kit is supplied with the room and must be fitted. The kit for a
standard room includes a light, a light switch, an external indicator and a bell
alarm. In addition to the items mentioned above, combo rooms with internal
access doors are also supplied with an electronic man in room (MIR) alarm,
and additional lighting and external indicators as required.
Australian standards require the light and light switch to be fitted inside the
room, and the external indicator fitted outside the room. The external
indicator illuminates when the light is on.
The light should be mounted inside the room (typically on the ceiling), the
light switch should be mounted inside the room next to the door, and the
external indicator should be mounted beside the door on the outside of the
room.
The alarm bell must be fitted to the door (follow instructions included with the
bell). Combo rooms must have the MIR alarm fitted to the room with internal
access (follow instructions included with the MIR alarm).
The compliance kit must be wired up by a licenced electrician (see diagrams
below).
Note:
If the unit is fitted with a light, the unit light must be disconnected or
removed. The compliance kit light switch must be the only available light
switch for the room.
Legend
No.
Description
1
Room with external door
2
Room with internal door
3
Light
4
External indicator
5
Light switch
6
Electronic MIR alarm
P N
Standard room
1
3
4
5
P
N
Combo room
1
2
3
3
4
5
5
4
6