Operation

User Manual

SKOPE B1200-2/B1200G-2

Temperature

Setpoint

The chiller temperature setpoint is factory set at 1°C. If necessary the 
standard setting can be adjusted between 0°C and 4.0°C. SKOPE do not 
recommend that the setpoint be changed unless it is absolutely necessary, 
and then only by small increments at a time.

To adjust the setpoint

Perishable

Mode

The chiller has the ability to operate in either perishable mode or non-
perishable mode. When in perishable mode the 

 symbol on the EMS 

controller faceplate is lit red, when in non-perishable mode the 

 symbol is 

not lit.
Perishable mode is for use with perishable products such as dairy or food 
products. When in perishable mode the chiller temperature is kept 
constantly cool at all times. During standby periods the lights switch off and 
the fans cycle on and off. Perishable mode must be used when perishable 
product is being stored inside the chiller.

Non-perishable mode is for use with non-perishable products such as 
carbonated drinks and water. When in non-perishable mode, the chiller 
temperature is moderated, the lights switch off and the fans cycle on and off 
during standby periods resulting in maximum energy savings. Follow the 
steps below to change between perishable and non-perishable mode.

To change between perishable and non-perishable mode

1. Push and hold the 

set

 button, 

PAS

 

appears on the display.

2. Release the 

set

 button.

3. Push the 

set

 button four times.

4. Push the 

up

 button once.

5. Push the 

down

 button twice.

6. Push the 

defrost

 button twice.

7. Push the 

down

 button to nagivate 

to the parameter menu. 

PS

 will 

show on the display.

8. Push the 

set

 button to enter the parameter menu.

9. Push and hold the 

set

 button to scroll through the parameter menu.

10. Release the set button when 

SPC

 

appears on the display.

11. Push the 

up

 and 

down

 button to change the value.

12. Once the desired mode setting is flashing on the display, leave the controller 

for 20-30 seconds to save the setting. 

Set

Defrost 

Up

Down 

IMPORTANT

Ensure perishable mode is used when perishable product is being 

stored inside the chiller.

1. Push and hold the 

set

 button, 

PAS

 

appears on the display.

2. Release the 

set

 button.

3. Push the 

set

 button four times.

4. Push the 

up

 button once.

5. Push the 

down

 button twice.

6. Push the 

defrost

 button twice.

Continued over page

Set

Defrost 

Up

Down 

Содержание B1200-2

Страница 1: ...B1200 2 B1200G 2 User Manual MAN10364 Rev 3 3 Mar 2014 B1200G 2 SKOPE Two Door Vertical Chiller B1200 2 no sign G12EV X5621 B1200G 2 lit sign G12EV...

Страница 2: ...land SKOPE 1 year Extended Warranty Extend your Warranty Protection by 1 year during registration Please check you have not already organised an extended warranty through your dealer at time of purcha...

Страница 3: ...om Shelves 6 Wire Shelves 6 2 Operation Automatic Start Up 7 Loading Product 7 EMS Controller Operations 8 Introduction 8 Self Learning 8 Motion Sensor Door Switch 8 Faceplate 9 Temperature Setpoint 1...

Страница 4: ...ssential to economical high performance Be careful not to touch moving parts and hot surfaces For your own safety and that of others ensure that all electrical work is done by authorised personnel If...

Страница 5: ...from overflowing Ventilation Ensure there is always at least a 50mm gap around the back top and underside of the cabinet Keep the ventilation slots in the front panel clear at all times never store ca...

Страница 6: ...may be fitted at different heights to suit various products Each shelf is held in place with four shelf clips which engage in the shelf support strips The support strips are numbered for easy location...

Страница 7: ...elves because this might stop the doors from shutting or even break something Item Activity Condenser Fan The condenser fan starts when the chiller is plugged in Lighting The lights that illuminate th...

Страница 8: ...t shopping activity and updating itself A service agent is not required if the store hours change or you disconnect the power to move the chiller The EMS Advanced controller continuously collects data...

Страница 9: ...the compressor light green when on 5 LED for the evaporator fan green when on 6 LED indicating perishable mode red when on See page 10 for more information 7 LED linked to the motion sensor and flash...

Страница 10: ...ture is moderated the lights switch off and the fans cycle on and off during standby periods resulting in maximum energy savings Follow the steps below to change between perishable and non perishable...

Страница 11: ...pen over two minutes an alarm sounds but stops when the door closes again If the door remains open five minutes such as when loading product then the alarm stops and the EMS Advanced controller turns...

Страница 12: ...olated from the power supply before cleaning Condenser Coil To ensure trouble free performance we strongly urge monthly cleaning with a soft brush to remove dust and fluff A more thorough cleaning is...

Страница 13: ...late the chiller from the mains power supply see previous page 2 Remove the diffuser by squeezing it until it is released from the aluminium housing and then push the diffuser out of the way 3 Rotate...

Страница 14: ...of the sign assembly 6 Loosen the two outside screws vertical slot screws and slide the lampholder brackets and LED tube to the bottom of the vertical slots 7 Rotate and remove the failed LED tube 8...

Страница 15: ...higher than expected Unit operating too hot Clean the condenser coil see page 12 Ensure the cabinet has good ventilation around the refrigeration unit see page 5 Ensure the cabinet is in a cool spot...

Страница 16: ...after their state condition get up or packaging has been altered in any manner Alters removes including part removal or obliterates including part obliteration the trade mark on the product Applies a...

Отзывы: