73
SKOPE TME ActiveCore
Replacement Procedures
Service Manual
Compressor
Electrics
The compressor electrics are located on the front of the compressor (see
image below).
To access the compressor electrics, remove the refrigeration unit (see
page 66) and unit cover (see page 69). The capacitor unclips from the relay
cover, and the relay cover unclips from the compressor.
Pressure
Switch
A manually resettable high pressure switch is fitted to protect the
refrigeration unit from over-pressure (high temperature) conditions.
Conditions that may activate the high pressure switch are:
High ambient conditions (ensure adequate ventilation)
Lack of refrigeration ventilation
Blocked or restricted condenser or condenser filter
Faulty condenser fan motor
Poor refrigeration unit sealing