HARDWARE
MTx
1 - 6 - 18
SKF Condition Monitoring Centre – Steyr
There is a possibility to connect other sensors with a voltage-output less than the 24V.
Thereto the gain of the input-amplifier is adjustable. By using the amplifier there is a pos-
sibility to get better resolution on the ADC.
For example:
Your sensor delivers only 0 V to 10 V the ADC will be used in a range of
so 0 V to 1,28V. If the amplifier with a gain of two (adjustable in the software) is used there
are 0 V to 2,56 V at the ADC and so a better resolution in the digital-converted results.
But be aware, if the input exceeds the 3,3 V the ADC will stuck at his maximum and maybe
information will be lost without any error.
Parameters in software
1. Name:
Description of the voltage sensor
2. Unit:
Unit description of the sensor
3. Sensitivity:
Defines the sensitivity of the used sensor in mV/measured unit.
4. Offset:
Defines the offset of the sensor in the measured unit
5. Gain:
Defines pre-amplification as described in the text above.
Voltage input
Input ............ Umax = 24 V
Sensor ......... maximum signal voltage USignalmax [V]
Gain depends on calculated x:
Examples
USignalmax = 10 V
-> chosen gain: 2
USignalmax = 7 V
-> chosen gain: 2
USignalmax = 3 V
-> chosen gain: 5
Gain
1 < x < 2
1
2 < x < 4
2
4 < x < 5
4
5 < x
5
10
V
7 8
----------
1 28
V
=
x
Umax
USignalmax
--------------------------------
=
x
24
10
------
2 4
=
=
x
24
7
------
3 4
=
=
x
24
3
------
8
=
=
Содержание MTx
Страница 2: ......
Страница 6: ...VERSION OF MANUAL MTx 1 6 4 SKF Condition Monitoring Centre Steyr Room for notes...
Страница 40: ...SOFTWARE MTx 1 6 38 SKF Condition Monitoring Centre Steyr Fig 4 19...
Страница 45: ...MTx SOFTWARE SKF Condition Monitoring Centre Steyr 1 6 43 Fig 4 29 Examples...
Страница 55: ...MTx SOFTWARE SKF Condition Monitoring Centre Steyr 1 6 53 Fig 4 44...
Страница 56: ...SOFTWARE MTx 1 6 54 SKF Condition Monitoring Centre Steyr Room for notes...
Страница 64: ...APPENDIX MTx 1 6 62 SKF Condition Monitoring Centre Steyr 5 4 DIMENSION DRAWINGS Fig 5 5...
Страница 65: ...MTx APPENDIX SKF Condition Monitoring Centre Steyr 1 6 63 Fig 5 6...
Страница 66: ...APPENDIX MTx 1 6 64 SKF Condition Monitoring Centre Steyr 5 5 DECLARATION OF CONFORMITY Fig 5 7...
Страница 67: ......