AC Cable Size
Before wiring the input and output of inverter, refer to table 2 for minimum recommended cable size and
torque value
Table 2. Recommended cable size and torque value for AC wire
Model Number
Typical
Amperage
AC Input
AC Output
Torque value
PL20 1KW 230Vac
10A
12AWG
14AWG
1.5~2.0 Nm
PL20 1.5KW 230Vac
12A
12AWG
14AWG
1.5~2.0 Nm
PL20 2KW 230Vac
PL20 1KW 110Vac
15A
12AWG
12AWG
1.5~2.0 Nm
PL20 3KW 230Vac
PL20 1.5KW 110Vac
20A
12AWG
12AWG
1.5~2.0 Nm
PL20 4KW 230Vac
PL20 2KW 110Vac
32A
12AWG
12AWG
1.5~2.0 Nm
PL20 5KW 230Vac
40A
12AWG
12AWG
1.5~2.0 Nm
PL20 6KW 230Vac
PL20 3KW 110Vac
50A
10AWG
12AWG
1.5~2.0 Nm
PL20 8KW 230Vac
PL20 4KW 110Vac
60A
10AWG
10 AWG
2.0~2.5 Nm
PL20 10KW 230Vac
PL20 5KW 110Vac
70A
8AWG
10 AWG
2.0~2.5 Nm
PL20 12KW 230Vac
PL20 6KW 110Vac
80A
6AWG
8AWG
2.0~2.5 Nm
AC Connections
Installation should be done by a qualified electrician. Consult local code for the proper wire sizes,
connectors and conduit requirements.
On the left of rear chassis is the AC hardwire cover. Two three-station terminal block is provided to make the
AC connections. The terminal block is used to hardwire the AC input, AC output, and ground. The National
Electrical Code requires that an external disconnect switch be used in the AC input wiring circuit. The AC
breakers in a sub panel will meet this requirement.
Содержание PL20 1.5KW
Страница 1: ...USER MANUAL PL20 Series Hybrid Inverter ...
Страница 12: ...10 Figure 9 PL204 6KW Back panel Figure 10 PL208 12KW Front panel Figure 11 PL208 12KW Back panel ...
Страница 17: ...15 6 DC AC Intelligent mode selection setting AC mode priority DC mode priority 7 Battery capacity setting ...
Страница 18: ...16 11 kinds of battery capacity settings 65AH 80AH 100AH 150AH 200AH 250AH 300AH 400AH 500AH 600AH 800AH ...