SJE-Rhombus
®
VARIOspeed
®
Micro Controller User Manual
15
Parameter List
No.
Content of parameter
Min.
Value
Max.
Value
Default
Value
Unit
Remarks
Change
during
operation
Set
Press
Operating Pressure
11
69
50
PSI
Target operating pressure
O
BR-01
Base frequency
50
60
60
Hz
X
BR-02
Max. Output
Frequency
35
80
60
Hz
X
BR-03
Min. Output
Frequency
20
50
30
Hz
O
BR-04
Rotating direction
0
1
0
Hz
0: Forward
1: Reverse
X
BR-05
Overload Auto Reset
0
99
1
Min.
0: Manual Reset
1-99: Auto Reset Time
BR-06
Transducer Offset
-5
5
0
PSI
O
BR-07
Restart after sleep
pressure difference
1
15
5
PSI
O
BR-08
High pressure alarm
51
99
70
PSI
O
BR-09
Low pressure alarm
0
15
10
PSI
O
BR-10
Frost Protection
0
99
0
Min.
0: unused
1-99: Time used
O
BR-11
Lock parameters
0
2
0
0: Changeable
1: Change N/A
2: Factory Default
X
BR-12
Firmware Revision
X
BR-13
Alarm Information
Able to record total 10 data
X
BR-14
Single or three phase
otor
1
3
1
1: 1 Phase
3: 3 Phase
X
BR-15
Sleep stop delay time
5
3.0
10
Sec.
Min.
X
BR-16
Low pressure restart time
0
30
0
Min.
X
BR-17
Pump FLA - MICRO D
0.0
9.0
7.2
Amps
Set to match motor max.
amperage
X
Pump FLA - MICRO D Plus
12.0
9.6
Caution:
Setting BR-14 & BR-17 incorrectly may result in permanent motor or VFD damage.