background image

INTERNAL WEIGHT

SENSOR FLOAT

®

 ONLY

1.   Determine desired activation level as 

shown in Figure B.

2.   Suspend switch 18 cm below desired 

activation level as shown in Figure F. 
Switch remains partially submerged 
during the "on" tipping action. Switch can 
be totally submerged and still continue 
to operate properly.

3.   Wire switch as shown in Figure D.
4. 

Check installation. Allow system to cycle 
to insure proper operation.

MOUNTING THE  SWITCH

WARNING:

 Do not install switch in direct line 

of incoming liquid.
1. 

Place the cord into the clamp as shown 
in Figure A. 

2.    Locate clamp at desired activation level 

and secure the clamp to the discharge 
pipe as shown in Figures B and C.    

Note: 

Do not install cord under hose 

clamp.

3.    Tighten the hose clamp using 

screwdriver.  Over tightening may result 
in damage to the plastic clamp. Make 
sure the float cable is not allowed to 
touch the excess hose clamp band 
during operation.

4. 

Wire switch as shown in Figure D.

5.   Check installation. Allow system to cycle 

to insure proper operation. 

Note: 

All hose clamp components are made 

of 18-8 stainless steel material. See your SJE 

Rhombus® supplier for replacements.

CABLE WEIGHT

1.   Determine desired activation level.
2.    Suspend switch and cable weight at desired 

activation level as shown in Figure E.

3.   Wire switch as shown in Figure D.
4.   Check installation. Allow system to cycle 

to insure proper operation. 

To adjust cable weight tether length:
1.  Release clip.
2.  Adjust cable weight to desired position.
3.  Lay switch cable in weight channel.
4.  Align clip with weight channel and slide 

towards switch cable as shown in Figure 
E.

5.  Snap clip snugly up to cable, moving clip 

to tightest possible position.

ELECTRICAL SHOCK HAZARD

Disconnect power before installing or servicing this 
product. A qualified service person must install and 
service this product according to applicable electrical 
and plumbing codes.

EXPLOSION OR FIRE HAZARD

Do not use this product with flammable liquids. 
Do not install in hazardous locations as defined by 
National Electrical Code, ANSI/NFPA 70.

Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged 

or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric Code, 

 ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable. 

Figure F

Figure A

Figure B

Sensor Float

® 

 

 

 

 

 

 

 

 

Figure D

125/250 VAC 

NORMALLY OPEN

125/250 VAC 

NORMALLY CLOSED

On SPDT models, insulate unused red or black wires with wire nut. Wire can become electrically hot.

In 230 VAC  installations, one side of the line going to the load is always 

HOT

. This condition exists if the switch is on or off.  Install double pole disconnect on all 230 VAC circuits.

Figure E

SJE SIGNALMASTER

®

 SPDT ONLY

SJE SIGNALMASTER

®

 EP

SJE SIGNALMASTER

®

 &

SENSOR FLOAT

®

Figure C

NORMALLY OPEN/NORMALLY CLOSED

SJE SignalMaster

®

SJE SignalMaster

®

 SPDT, 

and SJE SignalMaster

®

 EP

125/250 VAC EP MODELS

NORMALLY OPEN/NORMALLY CLOSED

Technical support: +1 800-746-6287

[email protected]

www.sjerhombus.com

Technical Support Hours: Monday-Friday, 7 A.M. to 6 P.M. Central Time

PN 1012081C 06/21 © 2021 SJE, Inc. All Rights Reserved. SJE RHOMBUS is a trademark of SJE, Inc.