CALIBRATING THE  MONITOR TO A  SPECIFIC TANK 

1.  Enter calibration mode by pressing and holding the "Alarm Level" and "Test/Silence" buttons for approximately 5 seconds or  
 

until the power LED light starts to blink as shown in 

Figure C

 

Note:

 While in the calibration mode, the power light will continue blinking.

2.    Bar graph will now display current tank set level by lighting up one LED. This is indicated with a percent from 10%-100%.  

See 

Table 1

 for available monitoring levels.

3.    To change the SJE Level Monitor

 CL monitoring level, push the "Set" button. This will toggle the light bar up one position.

4.  After desired monitoring level is lit, wait 10 seconds and the SJE Level Monitor

 CL will return to normal operating mode.

 

Note:

 During calibration mode, if at any time a button is not pushed within 10 seconds the unit will return to normal 

operating mode.

5.  Functionally test system each time calibration is changed to insure system is operating as expected.

  

ALARM SET POINTS MODE

SETTING THE MONITOR TO A HIGH LEVEL OR LOW LEVEL ALARM

The monitor can be set to be a 

high water

 or 

low water

 alarm. When set for high water, the alarm will activate when the liquid 

level rises above the set point. When set as a 

low water

 alarm, the alarm will activate when the liquid level falls below the set 

point. The default configuration for the alarm is for 

high water

 alarm. 

To change the configuration to perform the following steps:

1.   Disconnect power to the SJE Level Monitor

 CL and any product connected to auxiliary contacts as shown in 

Figure D

 on 

next page.

2.  Disconnect terminal block.

3.  Remove four corner screws on the front cover.

4.  Turn cover over to view the back as shown in 

Figure E

 on next page. Move jumper of J3 from pin 1 and pin 2 for 

high level

 

alarm to pin 2 and pin 3 for 

low level

 alarm.

5.  Reassemble alarm and reconnect terminal block.

6.  Connect power and test alarm to ensure system operates properly.

SET AND CHECK THE ALARM LEVEL 

To view the current alarm level press and hold the "Alarm Level" button as shown in 

Figure F

 on next page. The display will 

switch to single lit LED on the bar graph. The LED will be set to a percentage of total tank range set in calibration mode. 

If all 

LED bars are lit when the "Alarm Level" button is pushed the alarm is set to "Disable" mode which will disable the audible 

alarm, alarm LED, and auxiliary contacts.

To change the alarm set point:

1.  Enter alarm set point mode by pressing and holding the "Alarm Level" button for approximately 5 seconds or until the 

 

power LED light starts to blink as shown in 

Figure C

 

Note:

 While in the alarm set point mode, the power light will continue blinking.

2.    Bar graph will now display current tank set level by lighting up one LED. This is indicated with a percent from 10%-100%.  

 

All LED lights will indicate alarm is deactivated.

Figure C

For Tank Depths        For Tank Depths

(English)                   (English)

40 inch C-Level™     100 inch C-Level™

Choose this 

depth bar

10 to 12 inches           25 to 30 inches

10%

13 to 15 inches           31 to 37 inches

20%

16 to 18 inches           38 to 45 inches

30%

19 to 21 inches           46 to 52 inches

40%

22 to 24 inches           53 to 60 inches

50%

25 to 27 inches           61 to 67 inches

60%

28 to 30 inches           68 to 75 inches

70%

31 to 33 inches           76 to 82 inches

80%

34 to 36 inches           83 to 90 inches

90%

37 to 40 inches          91 to 100 inches

100%

Table 1