INSTALLING THE  C-LEVEL

 SENSOR and SJE LEVEL MONITOR

™ 

CL

Caution: The C-Level

 sensor cable needs to run in separate conduit from the pump and power lines.  Operating temperature 

for the C-Level

 sensor is 32°F (0°C) to 120°F (50°C).

1.  Determine the normal operating levels for the configuration as shown in 

Figure A

.

2.    Position the C-Level

 sensor at the appropriate location on the pipe and secure the sensor and vent as shown in 

Figure D

 

Warning: Do not support the C-Level

 sensor by the cable. Position the sensor in the tank so that nothing is pushing on 

the diaphragm.

3.    Position the vent so that it is above the water level and stow the excess vent tube.

 

Warning: Do NOT kink or place black tubing under the hose clamp. Doing so will cause the sensor to fail.

4.  Tighten all hose clamps using a screw driver. Over-tightening may result in damage to the plastic parts.

 

Note:

 All hose clamp components are made of 18-8 stainless steel material. See your SJE Rhombus

®

 supplier for replacement 

parts.

5.  Mount the SJE Level Monitor

 CL in desired location.

6.  If using auxiliary contacts, connect wire to terminal block as shown in 

Figure B

.

 

ELECTRICAL SHOCK WARNING: Auxiliary contacts are designed for Class II circuit. Only use load meeting Class II circuit 

requirements.

7.  Calibrate SJE Level Monitor

 CL to desired range. See section "Calibrating the Monitor to a Specific Tank" for instructions 

on how to calibrate.

8.  Set alarm mode and level as desired. See sections "Alarm Set Points Mode" for instructions.

9.  Functionally test system by filling the tank and witnessing proper operation.

For detailed specifications on this product, or for the complete line of SJE Rhombus

®

 

panel, alarm, and switch products, visit our web site at www.sjerhombus.com.

ELECTRICAL SHOCK HAZARD

Disconnect power before installing or servicing this 
product. A qualified service person must install and 
service this product according to applicable electrical 
and plumbing codes.

EXPLOSION OR FIRE HAZARD

Do not use this product with flammable liquids. 
Do not install in hazardous locations as defined by 
National Electrical Code, ANSI/NFPA 70.

Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged 

or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric Code, 

ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable. 