Single Phase Simplex

SJE Rhombus

®

 Type  115

Installation Instructions and Operation/Troubleshooting Manual

Technical support: +1-800-746-6287

[email protected]

www.sjerhombus.com

    PN  1008706F  05/19                                                           

   © 2019 SJE, Inc. All Rights Reserved.

SJE RHOMBUS is a trademark of SJE, Inc.

Manufactured by:

Warranty void if panel is modified.

Call factory with servicing questions:

1-800-RHOMBUS

(1-800-746-6287)

This control panel must be installed and serviced by a licensed 

electrician in accordance with the National Electric Code NFPA-70, 
state and local electrical codes. 

All conduit running from the sump or tank to the control panel 

must be sealed with conduit sealant to prevent moisture or gases 
from entering the panel.  

NEMA 1 enclosures are for indoor use only,

 

primarily to provide a degree of protection against contact with en-
closed equipment.  Cable connectors are not required to be liquid-tight 
in NEMA 1 enclosures.  

Do not use NEMA 1 enclosures if subjected to 

rain, splashing water or hose-directed water.  NEMA 4X enclosures 
are for indoor or outdoor use,

 primarily to provide a degree of protec-

tion against corrosion, windblown dust and rain, splashing water and 
hose-directed water. 

Cable connectors must be liquid-tight in NEMA 

4X enclosures.

Standard Type 115 panels are designed to operate with two floats.  

These floats operate the pump and high level alarm functions.  Wide 

angle pump switch and SJE Double Float™ applications are illustrated 

on next page.  

NOTE: Options ordered may affect the number of floats and their 

functions. Please reference the schematic provided with the control 

panel for proper installation.

Installation of Floats

CAUTION: 

If control switch cables are not wired and mounted in the 

correct order, the pump system will not function properly.

WARNING:

 Turn off all power before installing floats in pump chamber. 

Failure to do so could result in serious or fatal electrical shock.

1. 

  Use float label kit to label floats for specific operation (stop, lead, 

lag, alarm, etc.). See schematic for float options.

2. 

  Determine your normal operating level, as illustrated in 

Figures 1 

& 2

.

3. 

  Mount float switches at appropriate levels as illustrated in 

Figure 

3

. Be sure that floats have free range of motion without touching 

each other or other equipment in the basin.

4. 

For mounting clamp installation: place the cord into the clamp as 

shown in

 Figure 3

. Locate the clamp at the desired activation level 

and secure the clamp to the discharge pipe as shown in 

Figure 3

 NOTE:

 Do not install cord under hose clamp.

5. 

  Tighten the hose clamp using a screwdriver. Over tightening may 

result in damage to the plastic clamp. Make sure the float cable is 

not allowed to touch the excess hose clamp band during operation.

NOTE:

  All hose clamp components are made of 18-8 stainless steel 

material. See your SJE Rhombus® supplier for replacements.

Installation

Содержание 115

Страница 1: ...perate the pump and high level alarm functions Wide angle pump switch and SJE Double Float applications are illustrated on next page NOTE Options ordered may affect the number of floats and their functions Please reference the schematic provided with the control panel for proper installation Installation of Floats CAUTION If control switch cables are not wired and mounted in the correct order the ...

Страница 2: ... TO STEP 11 FOR INSTALLATION REQUIRING A SPLICE FOLLOW STEPS 6 10 Installation Instructions 6 Determine location for mounting junction box according to local code requirements Do not mount the junction box inside the sump or basin 7 Mount junction box to proper support 8 Run conduit to junction box Drill proper size holes for the type of conduit used Attach connectors to junction box 9 Identify an...

Страница 3: ... the liquid level travels beyond the pump switch or Double Float and reaches the alarm float the audio visual alarm will be activated The alarm horn can be silenced by moving the test normal silence switch to the silence position Alarm System Horn and Indicator When an alarm condition occurs a red light and a horn will be activated If the test normal silence switch is moved to the silence position...

Страница 4: ...ight does not activate replace light with same type Circuit Breaker optional Check each pole of the circuit breaker for proper resistance reading using the following procedure WARNING Disconnect incoming power to panel 1 Isolate the circuit breaker by disconnecting either line side or load side wires 2 Place the ohmmeter leads across the corresponding line and load terminals of each pole 3 With th...

Отзывы: