
452164.66.02 · FD 9211
EN-3
English
SMLA-XP-11TAS - SMLA-XP-16TAS
2 Purpose of the heat
pump
2.1 Application
The air-to-water heat pump is to be used exclusively for the heat-
ing of heating water. It can be used in newly built or previously
existing heating systems.
The heat pump is suitable for mono energy and bivalent opera-
tion down to an external temperature of -25 °C.
Proper defrosting of the evaporator is guaranteed by maintaining
a heating water return flow temperature of more than 18 °C dur-
ing continuous operation.
The heat pump is not designed for the increased heat consump-
tion required when a building is being dried out. The additional
heat consumption should be met using special devices provided
by the customer. If a building is to be dried out in autumn or win-
ter, we recommend installing an additional heating element
(available as an accessory).
NOTE
The device is not suitable for operation with a frequency converter.
2.2 Operating principle
Surrounding air is drawn in by the ventilator and fed via the evap-
orator (heat exchanger). The evaporator cools the air, i.e. it ex-
tracts heat from it. This extracted heat is then transferred to the
working medium (refrigerant) in the evaporator.
The heat is “pumped” to a higher temperature level by increasing
its pressure with the aid of an electrically driven compressor. It is
then transferred to the heating water using the liquifier (heat ex-
changer).
Electrical energy is used to raise the temperature of the heat in
the environment to a higher level. Because the energy extracted
from the air is transferred to the heating water, this type of device
is called an air-to-water heat pump.
The air-to-water heat pump consists of the main components
evaporator, ventilator and expansion valve, as well as the low-
noise compressor, liquifier and electrical control system.
At low ambient temperatures, humidity accumulates on the evap-
orator in the form of frost reducing the transfer of heat. Uneven
accumulation during this process does not indicate a fault. The
evaporator is defrosted automatically by the heat pump as re-
quired. Steam may be emitted from the air outlet depending on
the atmospheric conditions.
3 Scope of delivery
3.1 Basic device
The heat pump contains the components listed below.
The refrigerant circuit is hermetically sealed. It contains the
Kyoto protocol approved refrigerant R404A with a GWP value of
3784. It is CFC-free, does not deplete ozone and is non-flamma-
ble.
1)
Evaporator
2)
Ventilator
3)
Filter dryer
4)
Switch box
5)
Managers
6)
Liquifier
7)
Expansion valve
8)
Compressor
Содержание SMLA-XP-11TAS
Страница 2: ......
Страница 22: ...EN 10 452164 66 02 FD 9211 English SMLA XP 11TAS SMLA XP 16TAS...