background image

 

 

   

 

 

Document NO.:RD-519-39-001 

 

   

Version: A    2018.04.20 

- 4 - 

product (see Diagram 3). 

 

 

 

 

 

 

 

              Diagram 3 

 

While the first unit base LED is On, press wireless test 

button on the other unit wireless base of smoke alarm units 3 

times within 2 seconds, and ensure the LED flashing 3 times 

to indicate

 successful interconnection. 

 

Repeat step 

  on all other units. 

 

Wait about 2 minutes until the first unit base LED goes 

out or press the base button 3 times in 2 seconds  to exit 

“Learning  mode ".  When  all units have been paired,  press 

and hold the Test / Hush button at least 10 seconds. Check all 

other wireless interconnected units has received the RF signal 

and sounded  the alarm. Wireless interconnection is not 

completed until the function has been checked on each unit. 

 

2. Exit wireless interconnection 

Press the wireless test button for 3 times within 2 seconds. 

When the red LED on press and hold the wireless test button 

until the red LED flashing  5 times then  off.  Release the 

button to finish Exit wireless interconnection. 

 

3. Mixed inter connection setup 

Follow  the below procedure and notes if combining both 

wired and wireless interconnection methods in one 

application. 

 

Follow Wired Interconnection Setup for each group of 

wired units to complete the wiring installation. 
NOTE: install only one GS519 wireless base per group of 
wired interconnected units (Refer to

 

Diagram 7). 

 

Follow the Wireless Interconnection Setup to finish the 

pairing on all GS519 wireless bases. 

 

Select one smoke alarm in each wired group separately 

and press and hold the TEST/HUSH button  more than  10 

seconds. Check that all wired and wireless interconnected 

units sound and then stop approximately after 20 seconds has 

elapsed. 

Note: GS519 ,  GS517E  and  GS518E can be interconnected. 

Trouble shooting: 

Problem 

Cause and Remedy 

 

 

The green LED does 

not light when AC 

power supply. 

1. Check  the AC terminal  and the 

power cord  is properly connected 

to the smoke alarm.   

2. If  the problem still exists, please 

it return to your retailer. 

3. If  the unit is out of warranty, 

please replace another new alarm. 

 

 

Smoke alarm does not 

sound when testing. 

NOTE: Push test 

button  at least five 

seconds while testing! 

1. Ensure  the battery,  the AC 

terminal  and the power cord  have 

been properly connected. 

2. Clean smoke alarm. 

3. If there are still failures during 

warranty  Please  return  it  to your 

retailer. 

4. If the unit is out of warranty

 

please replace another new alarm. 

The 

alarm chirp 

occurs about every 32 

seconds meantime the 

red LED flashes once. 

The battery is in low voltage. Please 

replace battery and refer to “replace 

battery” section. 

The base flashes 

about 

every 

10 

seconds. 

The base battery is in low battery 

status. Please replace the base. 

Smoke alarm chirp   

occurs about every 32 

seconds

alarm goes 

into fault mode

1. Clean  smoke alarm.  Please refer 

to 

the “maintenance and 

cleaning” section. 

2.  Purchase and change another 

smoke alarm if the problem still 

exist. 

Smoke  alarm sounds 

unwanted 

alarming 

intermittently or 

sounds 

when 

residents are cooking, 

taking showers, etc. 

1. Press test button to pause alarm. 

2. Clean smoke alarm device. Please 

refer to the “maintenance and 

cleaning” section. 

3. Move smoke alarm device to new 

location and press test button. 

 

The alarm sounds 

different 

from 

normal. It starts and 

stops. 

1. Clean smoke alarm device. Please 

refer to the “maintenance and 

cleaning” section. 

2. If  there are still failures during 

warranty. Please return  it  to your 

retailer. 

3.  if the unit is out of warranty

 

please replace another new alarm. 

Содержание GS519

Страница 1: ... as near to the living areas as possible and ensure the alarm is audible when the bedrooms are occupied Typical single storey dwelling with recommended Install a smoke alarm on the ceiling inside each bedroom and in the hallway outside each separate sleeping area If a bedroom area hallway more than 30 feet long install a smoke alarm at each end If there s a basement install a smoke alarm on the ba...

Страница 2: ...on it is possible that the smoke alarm may fail at any time For this reason you must test the smoke alarm weekly and replace unit after 10 years Battery Specification Voltage DC 9V Alkaline Carbon Zinc Lithium battery Gold Peak GP1604S Carbon Zinc Battery Gold Peak GP1604A Alkaline Battery Raymax 6LR61 Alkaline Battery EVE CR9V P Lithium battery Voltage DC 3V Lithium battery GP Energy CR123A Lithi...

Страница 3: ...ill flash every 8 seconds indicating the smoke alarm is in the alarm silencer Hush mode NOTE WEEKLY TESTING IS REQUIERED Alarm silence hush mode When you press same Test button for at least 5 seconds or until the unit sounds to active silence control the alarm will enter HUSH mode for approx 8 minutes Smoke alarms are designed to minimize false alarms Combustion particles from cooking may set off ...

Страница 4: ...op approximately after 20 seconds has elapsed Note GS519 GS517E and GS518E can be interconnected Trouble shooting Problem Cause and Remedy The green LED does not light when AC power supply 1 Check the AC terminal and the power cord is properly connected to the smoke alarm 2 If the problem still exists please it return to your retailer 3 If the unit is out of warranty please replace another new ala...

Страница 5: ... not to open the door if the door is hot Teach household members to crawl along the floor to stay below dangerous smoke fumes and gases Practice a fire drill at least every six months including fire drills at night Ensure that small children hear the alarm and wake when it sounds They must wake up in order to execute the escape plan Practice allows all occupants to test your plan before an emergen...

Страница 6: ...ween 500mm and 1500mm from the highest point of the ceiling See Diagram 5 For single floor plan and multiple floor plan please refer to Diagram 6 Diagram 6 Wiring Instructions The appropriate power source is 220 240V single phase supplied When install or remove the smoke alarm you must turn off the AC power to ensure safety Connecting wires are recommended to use a cross sectional area from 0 8 mm...

Страница 7: ... should be lit when the alarm is operating from AC power Test smoke alarm using test button The alarm will sound 3 short beeps 1 5 seconds pause Then repeat it until release the button WARNING To prevent injury this unit must be securely attached to ceiling in accordance with the installation instructions Service and Warranty Company warrants to the original consumer Purchase each new smoke alarm ...

Отзывы: