Product User Manual Rev. 2.A - Cod. 14168.001.00D.005.002.A 

Release date: 20/03/2021 

 

For any technical information, please contact the technical service via email 

[email protected] 

 

 

 

 

 

 

Sitec S.r.l. reserves the right to revise this document if necessary, without notice, in order to adapt it 
to future developments and / or new business needs. Without ex
press authorization, the disclosure 
of this document, even if partial, is prohibited. Moreover, Sitec S.r.l. accepts no responsibility arising 
from the use of this document.

 

 

SITEC S.r.l. 

Industrial Electronics 

Via Antonio Tomba, 15  

36078 Valdagno (VI) - ITALY 

Tel. +39 0445 431576   Fax. +39 0445 439588 

Internet: www.teleletture.it    E-mail  in-
[email protected] 

Содержание TRG 72x72

Страница 1: ...SITEC S r l Industrial electronics www sitecsrl it User Manual TRG 72x72 R2 A Pag 1 USER MANUAL 72X72 TRG 72 x 72 Thermoregulator for ovens ...

Страница 2: ......

Страница 3: ...ICAL 9 ELECTRICAL 9 OUTPUTS K1 K2 9 ENVIRONMENTAL 9 3 2 FACTORY SETTINGS 10 4 0 CONFIGURATION MENU 11 4 1 MENU CONFIGURATION KEYS 11 4 2 HOW TO ENTER EXIT SURF THE CONFIGURATION MENU 11 4 3 MENU HIERARCHICAL SCHEME 12 5 0 SETTING PARAMETERS 13 5 1 SET THE SETPOINT TEMPERATURE 13 5 2 CHANGE THE TEMPERATURE PROBE 13 5 2 1 Operational range of the temperature probes 13 5 3 CHANGE THE TYPE OF SETTING ...

Страница 4: ......

Страница 5: ...rature to enable the second heater Minimum time to restart the heater heaters Instead with the PID setting single action you can set the following parameters Proportional band Integral time Derivative time Period of the output PWM signal In addition three different kinds of temperature probes are supported and they can be selected through the thermoregulator menu Thermocouple K Thermocouple J PT10...

Страница 6: ...NS 72 72 81 15 4 24 67 4 DIS N 052 rev 0 TC PT100 K1 K2 1 2 3 4 5 6 7 8 9 10 11 12 66 8 4 14 6 11 6 14 6 31 6 Please note dimensions are expressed in millimeters 11 LEDs for the setpoint position N 3 7 segment displays Scale of the setpoint temperature Rotating ring nut to set temperature With the IP54 protection class 2 Status LEDs for the relay outputs Setpoint LED ...

Страница 7: ...has adequate ventilation and avoid installation in containers that house devices that may cause the instrument to operate outside the stated temperature limits Install the instrument as far away as possible from sources of electromagnetic disturbances such as motors remote control switches relays solenoid valves etc 2 2 TERMINAL BOXES AND CONNECTION ELECTRICAL SCHEME 1 Clips to connect the thermor...

Страница 8: ...bles are screened it is advisable to connect them to the ground on one side only Finally it is recommended to check that the set parameters are the right ones and that the application works correctly before connecting the outputs to the actuators in order to avoid plant anomalies which may cause damage to people things or animals Sitec S r l and its legal representatives accept no responsibility f...

Страница 9: ...0 g Provided with connectors and hooks Terminal box connections Screw terminal Max 1 5 mm 2 cable Assembly Assembly within a device ELECTRICAL Supply voltage 24 VAC DC 10 50 60 Hz Max power demand 250 mA OUTPUTS K1 K2 Max electrical load 6 4 A AC1 AC3 Max voltage 230 V Vac Electrical operations 5x10 5 Mechanical operations 10 7 ENVIRONMENTAL Temperature of operation From 0 to 60 C Temperature of t...

Страница 10: ...robe tEr Thermocouple K rEG Type of setting OnF On Off setting Hy5 1nF Lower Hysteresis 0 C Hy5 5UP Upper Hysteresis 0 C T5H Temperature to start the second heater 0 C Ctr Control temperature 0 C Pb Proportional band 50 C 1nt Integral Time 200 s dEr Derivative Time 50 s Cyt Period of the PWM signal 20 s LP5 Min time to reactivate the outputs 0 s ...

Страница 11: ...ue 4 2 HOW TO ENTER EXIT SURF THE CONFIGURATION MENU To access the thermoregulator configuration menu simply press once any one of the OK keys beneath the thermoregulator To exit the configuration menu you have to go back all the menu hierarchy while pressing the OK EXIT keys or you can wait 10 seconds without pressing any button then the thermoregulator will automatically close the configuration ...

Страница 12: ... to 20 C T5H Temperature to start the second heater Visible only with On Off setting o From 0 C to full scale temperature Ctr Control zone Visible only with On Off setting o From 0 C to full scale temperature Pb Proportional Band Visible only with PID setting o From 1 to 999 C 1nt Integral Time Visible only with PID setting o From 0 to 999 seconds dEr Derivative Time Visible only with PID setting ...

Страница 13: ...tor K J if you want to use the thermoregulator J or Pt1 if you want to use the PT100 then confirm your choice by the OK key Once the change is done exit the menu and connect the temperature probe you have just selected to the clips of the thermoregulator see paragraph 2 2 than check that the thermoregulator doesn t signal any er ror see paragraph 6 1 Please note for the thermocouple K or J be sure...

Страница 14: ...tervention of the final setting element that in case of a relay could rapidly wear out 5 3 2 PID Setting The temperature setting via PID allows to obtain an accuracy significantly higher than the simple On Off control the calculation of the PID is done by adding the contributions of the proportional see paragraph 5 7 integral see paragraph 5 8 and derivative effect see paragraph 5 9 In this case b...

Страница 15: ...imprecision and weak fluctuations around one single threshold value The regulator behaves in the following way Deactivate K1 and or K2 see paragraph 2 2 when the temperature of the oven is higher than the setpoint higher hysteresis Activate K1 and or K2 when the temperature of the oven is lower than the setpoint lower hys teresis If the oven temperature is higher than the setpoint lower hysteresis...

Страница 16: ...perature to enable the second heater both the outputs K1 and K2 to set the temperature are always used Therefore starting both the outputs when the oven temperature is lower than the setpoint lower hysteresis temperature and deactivating both the outputs when the oven temperature is higher than the setpoint higher hysteresis temperature When the setpoint temperature is lower or equal to the temper...

Страница 17: ...her than the setpoint control area temperature and lower than the setpoint lower hysteresis temperature then only the output K1 is enabled If the oven temperature is lower than the setpoint control area temperature and than the set point lower hysteresis temperature then are enabled both the K1 and K2 outputs In order to deactivate the control area you just have to set it to zero while in order to...

Страница 18: ...rature is higher than the setpoint temperature If you reduce the proportional band the accuracy of the controller improves since a smaller error is enough to cause a certain change in the output power There is however a limit to the reduction of the proportional band at a certain point the system starts to self oscillate and the band must be increased In the diagram you can see how the power duty ...

Страница 19: ... integral control the output power increases as long as the temperature is equal to the setpoint At this point the out put of the integrator stops increasing and keeps a steady power The integral control is characterized by the Integration time described as the time necessary in order for the integral output to vary from zero to its maximum in the presence of a fixed error equal to the proportiona...

Страница 20: ...nal and integral is independent from the setpoint namely the derivative gives a contribution only according to the changing speed of the feedback without considering the setpoint position therefore a step change of the setpoint will not involve any change on the derivative To disable the derivative time you have to set it to 0 Please note the derivative time can be set up only after having enabled...

Страница 21: ...od can be set up only after having enabled the temperature setting via PID see paragraph 5 3 Hereafter the diagram shows a typical behaviour of the PID with PWM output 5 11 MINIMUM TIME TO REACTIVATE THE OUTPUTS To set up the minimum time to reactivate the outputs you have to enter the configuration menu see para graph 4 2 enter the LP5 level see paragraph 4 3 and then select the desired value and...

Страница 22: ...rmoregulator operational range then restart the thermoregulator E 4 The external temperature temperature probe of the oven is in under range lower than 0 C Check that the oven temperature is higher than 0 C otherwise the problem is as cribed to a malfunctioning of the temperature probe connected with the thermoregulator E 8 The external temperature temperature probe of the oven is in over range Ch...

Страница 23: ......

Страница 24: ...evise this document if necessary without notice in order to adapt it to future developments and or new business needs Without express authorization the disclosure of this document even if partial is prohibited Moreover Sitec S r l accepts no responsibility arising from the use of this document SITEC S r l Industrial Electronics Via Antonio Tomba 15 36078 Valdagno VI ITALY Tel 39 0445 431576 Fax 39...