INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
TYPE WBK & WBG
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
TYPE WBK & WBG
INDUSTRIAL AIR HEATERS TYPE WBK & WBG
Page 12 of 24
INDUSTRIAL AIR HEATERS TYPE WBK & WBG
Page 13 of 24
2. SAFETY STIPULATIONS
Connection of the air heater to the power supply must be performed by a qualified electrician and must be in
conjunction with local prescribed standards and safeguarded accordingly.
• The air heater is protected against overheating by means of a build-in maximum thermostat with a fixed value of
85°C and will reset automatically.
• Switching on the heater is to be performed by a special main switch or a suitable power plug – wall socket
combination.
• The air heater must have separate fuses in the main circuit.
• The air heater is suitable for either wall or floor mounting in normal surroundings with ‘not combustible materials’.
This in compliance the directives according to the NEN 1010. Do not use solvents or light inflammable materials in
the vicinity of the air heater.
• Touching of hot heating elements must be prevented from occuring.
• Operation must only be executed by trained personnel who have read and will adhere to the operating and
safety instructions.
To prevent fire hazards the rear end of the heater must be placed
110 mm from the wall
and 300 mm at the front
and 100 mm on both sides
and minimum 110 mm at the top
When commencing maintenance or other jobs
Let the heater cool down first and switch of Voltage at the mains
3. TECHNICAL SPECIFICATIONS
3.1
Technical specifications industrial air heater type WBG
3.2 Elements
3.3
Ventilator
3.4 Enclosure
3.5
General
Capacity
6kW
9kW
12kW
15kW
Temperature rise
25°C
38°C
25°C
32°C
Fuses
16A
16A
20A
25A
Amount
6 x 1000W
6 x 1500W
6 x 2000W
6 x 2500W
Material
AISI 321
AISI 321
AISI 321
AISI 321
Tube diameter
Ø8.5 mm
Ø8.5 mm
Ø8.5 mm
Ø8.5 mm
Element Voltage
230V
230V
230V
230V
Connection
3 x 400V (Y)
3 x 400V (Y)
3 x 400V (Y)
3 x 400V (Y)
Tension
230V
230V
230V
230V
Rating
10W
10W
16W
16W
Rpm’s
1300/min
1300/min
1300/min
1300/min
Air supply
650m³/h
650m³/h
1300m³/h
1300m³/h
Diameter
254 mm
254 mm
300 mm
300 mm
Material
Electrolytically zinc coated sheet steel, epoxy coated dark red (RAL 3011)
Execution
Fitted with a mounting bracket suited for wall mounting.
Dimension
440 x 430 x 500 mm (LxWxH)
Weight
16.5 - 17 kg
Cable glands
PG16 / PG16 for 6 and 9 kW - PG21 / PG16 for 12 and 15 kW
Tension
3x400 Volts 50Hz (+N)
Safety
Maximum safety thermostat 85°C (automatic) in combination with a
3-pole magnetic switch (coil voltage: 400 VAC).
Mounting
The mounting bracket is suited for wall mounting and has the ability
to hold the heater at a variety of angles.
Ambient thermostat
The heater has been fitted standard with terminals (pos. 1 and 2,
see electrical wiring diagram) for connecting an external ambient
thermostat. This thermostat must be able to switch the rating of the
heater (400 Volts)
Motor thermostat
Preheating and cooling down takes place with the aid of a motor
thermostat. When the heater is switched on it first preheats before
the ventilator starts running.
Additionally when it is switched of by an ambient thermostat the
heater will leave the ventilator running until the heater has cooled
down enough for the motor thermostat to switch it off.