- 29 -
if shutdown is required:
(1) To find the location of the shutdown register in the accessory protocol table protocol,
then send shutdown instructions to inverter.
(2) To confirm whether the inverter is in standby state.
(3) Turn off AC isolator S2 and AC breaker D3.
(4) Turn off DC breaker D1 of battery pack.
WARNING
After the electric circuits connected with the inverter are turned off, the
upper cover plate cannot be opened before DC capacitor in the
module fully discharged after 10 minutes.
To prevent personal injury, please use a multi-meter to measure the
voltage at wiring terminal if case maintenance or opening is
conducted. Only after ensuring that all the parts in the inverter is not
electrified, relevant operation can be conducted!
4.2 Monitoring interface information