Chapter IV Device Installation 15
Fig. 4-2 Installation space of storage inverter
4.4.5
Other requirements
1)
Waterproofing
The protection grade of the cabinet of the storage inverter is IP20. It is only installed and used in a dry and clean room. Water
leakage in room should be avoided so as to prevent the storage inverter from being damaged.
2)
Rat-proofing
After wiring, fireproofing mud should be used to seal inlet and outlet holes so as to meet the rat-proofing requirement.
Cabinet installation
After the cabinet is removed to the installation position of energy storing deice with a forklift or a tool. Fine adjust the cabinet
and remove it to the designed position, open the internal door of cabinet, use M13 screw to fix the cabinet, as shown in Fig.4-
3.
Fig.4-3. Diagram for cabinet base
When the cabinet needs to be fixed on the steel channel, Φ14 holes can be made in the steel channel. Fix the cabinet to the
steel channel with screws, as shown in Fig.4-4.
Fig. 4-4 Fix the cabinet to the steel channel Fig.4-5 Fix the cabinet to the concrete floor
cable
groove
Ground
Foot screw
Cable
groove
Fixed screw
Channel
steel
Содержание PWS1-500KTL-NA
Страница 1: ...Sinexcel PWS1 500KTL NA Grid Support Utility Interactive Energy Storage Inverter ...
Страница 2: ......
Страница 4: ......
Страница 7: ...Appendix 2 Quality assurance and after sales service 39 Installation Records 41 ...
Страница 8: ......
Страница 19: ...Chapter IV Device Installation 11 Fig 3 4 Appearance diagram for PWS1 500KTL NA storage inverter ...
Страница 34: ...26 第六章 操作控制显示面板 6 5 4 AC settings ...
Страница 35: ...27 Fig 6 7 AC settings ...
Страница 41: ...第六章 操作控制显示面板 33 ...
Страница 45: ...Chapter VII Communication Mode 37 Fig 7 5 Structure diagram for background monitoring system ...
Страница 49: ...Installation Records ...