3

 

Unit Placement 

3.1

 

Placement Considerations 

Unit placement should take account of the following considerations: 

 

Units should not be installed in the following locations: 

 

Where  exposure  to  direct  radiation  from  a  high-temperature  heat  source  or  to  interference  from  a  source  of 
electromagnetic radiation may occur. 

 

Where dust or dirt may affect heat exchangers. 

 

Where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.   

 

Where exposure to salinity may occur, such as seaside locations. 

 

Where highly flammable materials are present. 

 

Where exposure to oily air may occur, such as a kitchen. 

 

Where exposure to very high humidity may occur, such as a laundry. 

 

Units should be installed in positions where: 

 

The ceiling is horizontal and is able to bear the unit’s weight. 

 

There are no obstructions that could impede the airflow into and out of the unit. 

 

The airflow out of the unit can reach throughout the room. 

 

There is sufficient space for access during installation, servicing and maintenance. 

 

The  refrigerant  piping  and  drain  piping  can  be  easily  connected  to  the  refrigerant  piping  and  drain  piping 
systems. 

 

Short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) will not occur.   

 

3.2

 

Space Requirements 

Figure 3.1: Wall mounted space requirements (unit: mm)

 

SDV5-22HA, SDV5-28HA

 

SDV5-36HA, SDV5-45HA, SDV5-56HA

 

 

 

SDV5-71HA, SDV5-80HA, SDV5-90HA

 

 

 

 
 

 

 

 

 

Shape of indoor unit

440

835

280

45

186

Shape of indoor unit

990

53

315

335

375

Shape of indoor unit

561

1194

55

343

307

Содержание SDV5-22HA

Страница 1: ...INDOOR WALL MOUNTED UNITS SDV5 XXHA C O M M E R C I A L A I R C O N D I T I O N E R S S D V 5...

Страница 2: ...Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference...

Страница 3: ...3 1 Specifications 4 2 Dimensions 6 3 Unit Placement 7 4 Piping Diagram 8 5 Wiring Diagram 9 6 Capacity Tables 12 7 Electrical Characteristics 20 8 Sound Levels 21...

Страница 4: ...31 31 30 30 35 34 33 33 32 31 31 Sound power level dB A 46 45 45 45 44 44 44 46 45 45 45 44 44 44 48 47 47 46 46 45 45 50 49 48 48 47 46 46 Unit Net dimensions 5 WxHxD mm 835 280 203 990 315 223 Pack...

Страница 5: ...39 38 3 7 36 48 46 45 43 41 4 0 38 Sound power level dB A 53 52 51 51 50 4 9 49 59 58 57 54 53 5 2 51 59 58 57 54 53 5 2 51 63 61 60 58 56 5 5 53 Unit Net dimensions 5 WxHxD mm 990 315 223 1194 343 2...

Страница 6: ...6 2 Dimensions 2 1 Unit Dimensions Figure 2 1 Wall mounted dimensions unit mm SDV5 22HA SDV5 28HA SDV5 36HA SDV5 45HA SDV5 56HA SDV5 71HA SDV5 80HA SDV5 90HA...

Страница 7: ...midity may occur such as a laundry Units should be installed in positions where The ceiling is horizontal and is able to bear the unit s weight There are no obstructions that could impede the airflow...

Страница 8: ...iping diagram flare nut flare nut T2B gas side motor heat exchanger fan EXV liquid side T2 T1 Legend T1 Indoor ambient temperature sensor T2 Indoor heat exchanger mid point temperature sensor T2B Indo...

Страница 9: ...wing motor Electronic expansion valve Room temp sensor Mid pipe temp sensor Outlet pipe temp sensor Water level switch Connectors nted wiring diag gram CN7 CN30 CN22 CN21 ENC1 CN13 CN4 CN300 CN1 CN2 C...

Страница 10: ...alve Room temp sensor Mid pipe temp sensor Outlet pipe temp sensor Water level switch Connectors mounted wiring CN12 CN5 CN7 CN30 ON SW1 ON SW2 ENC1 ON SW3 CN20 diagram 1 2 1 2 1 2 1 2 ON SW4 1 2 ON S...

Страница 11: ...rvice eng g diagram CN9 1 2 ON SW1 CN17 CN11 SW8 CN18 C N 1 1 N 1 6 CN13 ntenance mu n accordance dance with a with all appli curely fasten ntenance the or electric sh y setting is f witch ENC1 m re t...

Страница 12: ...1 5 1 3 1 8 1 4 2 1 1 5 2 2 1 5 2 2 1 5 2 3 1 3 2 3 1 4 44 0 1 5 1 3 1 8 1 4 2 1 1 5 2 2 1 5 2 2 1 5 2 3 1 3 2 3 1 4 46 0 1 5 1 3 1 8 1 4 2 1 1 5 2 2 1 5 2 2 1 5 2 3 1 3 2 3 1 4 2 8 10 0 1 9 1 6 2 3...

Страница 13: ...4 2 3 3 6 2 4 3 7 2 4 3 8 2 3 3 8 2 1 44 0 2 5 1 9 2 9 2 1 3 4 2 3 3 6 2 4 3 7 2 4 3 8 2 3 3 8 2 1 46 0 2 5 1 9 2 9 2 1 3 4 2 3 3 6 2 4 3 7 2 4 3 8 2 3 3 8 2 1 4 5 10 0 3 1 2 4 3 7 2 6 4 2 2 8 4 5 2...

Страница 14: ...3 3 3 5 6 3 4 5 7 3 4 5 8 3 2 6 0 3 1 44 0 3 9 2 7 4 6 3 0 5 3 3 3 5 6 3 4 5 7 3 4 5 8 3 2 6 0 3 1 46 0 3 9 2 7 4 6 3 0 5 3 3 3 5 6 3 4 5 7 3 7 5 8 3 2 6 0 3 1 7 1 10 0 4 9 3 6 5 8 4 0 6 7 4 3 7 1 4...

Страница 15: ...4 9 7 5 5 3 8 0 5 5 8 1 5 3 8 3 5 0 8 6 4 9 44 0 5 5 4 4 6 6 4 9 7 5 5 3 8 0 5 5 8 1 5 3 8 3 5 0 8 6 4 9 46 0 5 5 4 4 6 6 4 9 7 5 5 3 8 0 5 5 8 1 5 3 8 3 5 0 8 6 4 9 9 0 10 0 6 2 4 9 7 3 5 3 8 4 5 8 9...

Страница 16: ...40 2 33 2 21 2 02 9 80 11 00 2 54 2 54 2 40 2 33 2 21 2 02 11 80 13 00 2 64 2 59 2 40 2 33 2 21 2 02 13 70 15 00 2 71 2 59 2 40 2 33 2 21 2 02 2 8 20 19 8 1 79 1 79 1 79 1 79 1 79 1 79 19 18 8 1 92 1...

Страница 17: ...3 68 3 36 9 80 11 00 4 24 4 24 4 00 3 88 3 68 3 36 11 80 13 00 4 40 4 32 4 00 3 88 3 68 3 36 13 70 15 00 4 52 4 32 4 00 3 88 3 68 3 36 4 5 20 19 8 2 80 2 80 2 80 2 80 2 80 2 80 19 18 8 3 00 3 00 3 00...

Страница 18: ...5 80 5 29 9 80 11 00 6 68 6 68 6 30 6 11 5 80 5 29 11 80 13 00 6 93 6 80 6 30 6 11 5 80 5 29 13 70 15 00 7 12 6 80 6 30 6 11 5 80 5 29 7 1 20 19 8 4 48 4 48 4 48 4 48 4 48 4 48 19 18 8 4 80 4 80 4 80...

Страница 19: ...0 8 73 8 28 7 56 9 80 11 00 9 54 9 54 9 00 8 73 8 28 7 56 11 80 13 00 9 90 9 72 9 00 8 73 8 28 7 56 13 70 15 00 10 17 9 72 9 00 8 73 8 28 7 56 9 0 20 19 8 5 60 5 04 5 60 5 60 5 60 5 60 19 18 8 6 00 5...

Страница 20: ...02 0 25 SDV5 28HA 50 220 240 198 264 0 32 15 0 02 0 25 SDV5 36HA 50 220 240 198 264 0 45 15 0 058 0 36 SDV5 45HA 50 220 240 198 264 0 47 15 0 058 0 37 SDV5 56HA 50 220 240 198 264 0 58 15 0 058 0 46...

Страница 21: ...in situ operation sound pressure levels may be higher as a result of ambient noise Figure 8 1 Wall mounted sound pressure level measurement 8 2 Octave Band Levels Figure 8 2 SDV5 22 28HA octave band...

Страница 22: ...enter frequency Hz Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 0 10 20 30 40 50 60 70 80 6...

Страница 23: ...SDV5 22 28HA Exploded View...

Страница 24: ...SDV5 36 45HA Exploded View...

Страница 25: ...SDV5 71 80 90HA Exploded View...

Страница 26: ...WALL MOUNTED UNITS SDV5 22 90HA C O M M E R C I A L A I R C O N D I T I O N E R S S D V 5...

Страница 27: ...SDV5 22HA...

Страница 28: ...00003568 1 10 Electronic control box 12122000004586 1 11 Air freshening filter 12100204000685 1 11 Air filter 12100204000626 2 12 Installation plate 12222000000012 1 13 Chassis assembly 12122000009005...

Страница 29: ...SDV5 28HA...

Страница 30: ...r unit main control board 17126000003568 1 10 Electronic control box 12122000004586 1 11 Air freshening filter 12100204000685 1 11 Air filter 12100204000626 2 12 Installation plate 12222000000012 1 13...

Страница 31: ...SDV5 36HA...

Страница 32: ...6 1 8 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000419 1 8 7 Fire proof Plate of Electrical Control Box CoverBox 12222000000391 1 8 8 Electric control box cover assembly 1222600000...

Страница 33: ...SDV5 45HA...

Страница 34: ...re joint 17400401002576 1 8 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000419 1 8 7 Fire proof Plate of Electrical Control Box CoverBox 12222000000391 1 8 8 Electric control box cov...

Страница 35: ...SDV5 56HA...

Страница 36: ...oint 17400401002576 1 8 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000419 1 8 7 Fire proof Plate of Electrical Control Box CoverBox 12222000000391 1 8 8 Electric control box cover a...

Страница 37: ...SDV5 71HA...

Страница 38: ...inal 17400401000020 1 9 5 Wire joint 17400401001516 1 9 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000380 1 10 Chassis assembly 12122000004184 1 11 VRF IDU display box assembly 1722...

Страница 39: ...SDV5 80HA...

Страница 40: ...inal 17400401000020 1 9 5 Wire joint 17400401001516 1 9 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000380 1 10 Chassis assembly 12122000004184 1 11 VRF IDU display box assembly 1722...

Страница 41: ...SDV5 90HA...

Страница 42: ...inal 17400401000020 1 9 5 Wire joint 17400401001516 1 9 6 Fire proof Plate of Electrical Control Box CoverBox 12222000000380 1 10 Chassis assembly 12122000004184 1 11 VRF IDU display box assembly 1722...

Страница 43: ...containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R410A The composition of the cooling med...

Отзывы: