,QVWDOODWLRQDQG0DLQWHQDQFH
6HUYLFH0DQXDO
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1)
Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring
points on the wall.
2)
Secure the mounting plate to the wall with screws.
6screws
Casing
Floor Installation
Wall Installation
Molding
3)
Once refrigerant piping and drain piping connections are complete, fill in the gap of the through hole with putty. A gap
can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes.
4)
Attach the front panel and front grille in their original positions once all connections are complete.
1)Cut the pipe end with a pipe cutter.
2)Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
3)Fit the flare nut on the pipe.
4)Flare the pipe.
5)Check that the flaring is properly made.
WARNING
1)
DO not use mineral oil on flared part.
2)
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3)
Never use piping which had been used for previous installations. Only use parts which are delivered with the unit.
4)
Do never install a drier to this R410A unit in order to guarantee its lifetime.
5)
The drying material may dissolve and damage the system.
6)
Incomplete flaring may cause refrigerant gas leakage.
Make sure that the
flare nut is fitted
The pipe end must
be evenly flared in
a perfect circle
Flare’s inner
surface must
be scratch-free
Cut exactly
at right
angles
Renove
burrs
Flaring
Set exactly at the position shown below
A
Die
A
0-0.5mm
1.0-1.5mm
1.5-2.0mm
Flare tool for R410A
Clutch-type
Clutch-type
(Rigid-type)
Wing-nut type
(lmperial-type)
Conventional flare tool
200m
m
5.
Flaring the pipe end
6screws
Содержание MS-P09AI
Страница 1: ...SERVICE MANUAL MS P09AI MS P12AI MS P18AI MULTI SYSTEM SERIE ...
Страница 2: ......
Страница 3: ...7HFKQLFDO QIRUPDWLRQ 6HUYLFH 0DQXDO 6XPPDU QGRRU 8QLW 3DUW ĉ 7HFKQLFDO QIRUPDWLRQ 5HPRWH RQWUROOHU ...
Страница 6: ...7HFKQLFDO QIRUPDWLRQ 6HUYLFH 0DQXDO 2XWOLQH LPHQVLRQ LDJUDP QGRRU 8QLW 8QLW PP 700 215 600 398 205 22 ...
Страница 28: ... QVWDOODWLRQ DQG 0DLQWHQDQFH 6HUYLFH 0DQXDO 0DLQWHQDQFH 0DOIXQFWLRQ LVSOD RI QGRRU 8QLW ...
Страница 29: ... QVWDOODWLRQ DQG 0DLQWHQDQFH 6HUYLFH 0DQXDO ...
Страница 46: ...PARTS GUIDE MULTI SYSTEM SERIE MS P 09AI MS P12AI MS P18AI ...